Parameters 361
Selects the type/source and scaling of actual value 1
transmitted to the fieldbus network through the embedded
fieldbus interface.
Auto
Type/source and scaling follow the type of reference 1
selected by parameter
. See the individual
settings below for the sources and scalings.
0
Transparent
The value selected by parameter
is sent as actual value 1. No scaling is applied (the 16-
bit scaling is 1 = 1 unit).
1
General
The value selected by parameter
is sent as actual value 1 with a 16-bit scaling of 100 =
1 unit (ie. integer and two decimals).
2
Torque
is sent as actual value 1. The scaling is
defined by parameter
3
Speed
is sent as actual value 1. The scaling
is defined by parameter
4
Frequency
is sent as actual value 1. The scaling
is defined by parameter
5
Position
Motor position is sent as actual value 1. See parameter
.
6
Selects the type/source and scaling of actual value 2
transmitted to the fieldbus network through the embedded
fieldbus interface.
Auto
Type/source and scaling follow the type of reference 2
selected by parameter
. See the individual
settings below for the sources and scalings.
0
Transparent
The value selected by parameter
is sent as actual value 2. No scaling is applied (the 16-
bit scaling is 1 = 1 unit).
1
General
The value selected by parameter
is sent as actual value 2 with a 16-bit scaling of 100 =
1 unit (ie. integer and two decimals).
2
Torque
is sent as actual value 2. The scaling is
defined by parameter
3
Speed
is sent as actual value 2. The scaling
is defined by parameter
4
Frequency
is sent as actual value 2. The scaling
is defined by parameter
5
Position
Motor position is sent as actual value 2. See parameter
.
6
EFB status word
transparent source
Selects the source of the status word when
is set to
.
Not selected
None.
0
Source selection (see
). -
Selects the source of actual value 1 when
is set to
Not selected
None.
0
Source selection (see
). -
No.
Name/Value
Description
Def
/
FbEq16
Summary of Contents for ACS880-x04
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 primary control program Firmware manual ...
Page 4: ......
Page 18: ...18 Using the control panel ...
Page 24: ...24 Control locations and operating modes ...
Page 112: ...112 Application macros ...
Page 496: ...496 Additional parameter data ...
Page 544: ...544 Fault tracing ...
Page 602: ...602 Control chain diagrams ...