Parameters 335
Source selection (see
). -
Specifies the currency used for the savings calculations.
Local currency
Local currency. The name of the currency can be edited by
choosing Menu - Settings - Edit texts on the control panel.
100
EUR
Euro.
101
USD
US dollar.
102
Defines a factor for conversion of saved energy into CO
2
emissions (kg/kWh or tn/MWh).
0.500
tn/MWh
0.000 … 65.535
tn/MWh
Factor for conversion of saved energy into CO
2
emissions.
1 = 1 tn/MWh
Actual power that the motor absorbs when connected direct-
on-line and operating the application. The value is used for
reference when energy savings are calculated.
Note:
The accuracy of the energy savings calculation is
directly dependent on the accuracy of this value. If nothing is
entered here, then the nominal motor power is used by the
calculation, but that may inflate the energy savings reported
as many motors do not absorb nameplate power.
0.0 kW
0.0 … 100000.0 kW Motor power.
See par.
Resets the savings counter parameters
Done
Reset not requested (normal operation), or reset complete.
0
Reset
Reset the savings counter parameters. The value reverts
automatically to
1
46
46 Monitoring/scaling
settings
Speed supervision settings; actual signal filtering; general
scaling settings.
Note:
The 16-bit scalings apply when parameter values are
read or written directly. With protocol- and profile-specific
read/write commands (eg. communication objects), the
scaling depends on the protocol or profile. See the
documentation of the adapter module.
Defines the maximum speed value used to define the
acceleration ramp rate and the initial speed value used to
define the deceleration ramp rate (see parameter group
). The speed acceleration and
deceleration ramp times are therefore related to this value
(
not
Also defines the 16-bit scaling of speed-related parameters.
The value of this parameter corresponds to 20000 in fieldbus,
master/follower etc. communication.
1500.00 rpm;
1800.00 rpm
(
b0)
0.10 … 30000.00
rpm
Acceleration/deceleration terminal/initial speed.
1 = 1 rpm
No.
Name/Value
Description
Def
/
FbEq16
Summary of Contents for ACS880-x04
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 primary control program Firmware manual ...
Page 4: ......
Page 18: ...18 Using the control panel ...
Page 24: ...24 Control locations and operating modes ...
Page 112: ...112 Application macros ...
Page 496: ...496 Additional parameter data ...
Page 544: ...544 Fault tracing ...
Page 602: ...602 Control chain diagrams ...