4
2
If the outer surface of the shield is non-conductive, turn the shield inside out and wrap
copper tape around the cable to keep the shielding continuous. Do not cut the grounding
wire (if any).
1
A
B
C
2
2
3
4
5
Stripped cable
A
Conductive surface of the shield exposed
B
Stripped part covered with copper foil
C
Cable shield
1
Copper foil
2
Shielded twisted pair
3
Grounding wire
4
Copper cable
5
4.
Push the cushions firmly together so that they press on the exposed cable shields.
Tighten the locking screws.
5.
Run the cables to their eventual connection points using existing trunking wherever
possible. Protect the cables against any sharp edges or hot surfaces.
6.
Strip the ends of the conductors. Try to keep the unshielded portion of the conductors
as short as possible. Use tape or shrink tubing to contain any stray strands. Connect
the conductors to the appropriate terminals. Twist the shields into a bundle, crimp a ring
terminal onto it and connect it to the nearest chassis grounding point.
7.
Refit any shrouds removed earlier.
42 Electrical installation
Summary of Contents for ACS880-607 Series
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 607 3 phase brake units Hardware manual ...
Page 2: ......
Page 4: ......
Page 8: ...8 ...
Page 12: ...12 ...
Page 30: ...30 ...
Page 32: ...32 ...
Page 36: ...36 ...
Page 44: ...44 ...
Page 54: ...54 ...
Page 62: ...62 ...
Page 66: ...66 Maintenance ...
Page 82: ...Dimension drawing bottom exit 82 Dimension drawings ...
Page 83: ...Dimension drawings 83 ...
Page 84: ...Dimension drawing top exit 84 Dimension drawings ...
Page 85: ... Dimension drawings 85 ...
Page 86: ......