Resistor connection
0…
U
1
3-phase symmetrical.
Voltage (U
2
)
For ACS880-104-xxxx-3 modules: This is indicated in the type designation label
as typical output voltage level 3x 0…566 VDC.
For ACS880-104-xxxx-5 modules: This is indicated in the type designation label
as typical output voltage levels 3x 0…566 / 679 / 707 VDC.
For ACS880-104-xxxx-7 modules: This is indicated in the type designation label
as typical output voltage levels 3x 0…742 / 849 / 976 (849 UL, CSA) VDC.
300 m (984 ft)
Maximum resistor cable
length
Busbars to quick connector: M12. Torque: 50 N·m (37 lbf·ft)
Output terminals
Busbars to support insulators: M8. Torque: 9 N·m (6.5 lbf·ft)
Cables to busbars: M12. Torque: 70 N·m (52 lbf·ft)
Efficiency
Approximately 98% at nominal power level.
Protection classes
IP22 (standard), IP42 (B054), IP54 (B055)
Degrees of protection
(IEC/EN 60529)
UL Type 1 (standard), UL Type 1 (B054), UL Type 12 (B055). For
indoor use only.
Enclosure types (UL50)
III, except for auxiliary power connections (fan, control, heating, lighting, cooling
unit pump etc) which are category II.
Overvoltage category
(IEC/EN 60664-1)
I
Protective class (IEC/EN
61800-5-1)
Ambient conditions
Environmental limits for the drive are given below. The drive is to be used in a heated,
indoor, controlled environment.
Transportation
in the protective package
Storage
in the protective package
Operation
installed for stationary
use
-
-
0…2000 m (0…6562 ft)
above sea level. For alti-
tudes over 2000 m, contact
ABB.
Installation site altitude
Output derated above 1000
m (3281 ft).
-40 to +70 °C (-
40 to +158 °F)
-40 to +70 °C (-
40 to +158 °F)
0 … +40 °C
(+32 … +104 °F). No con-
densation allowed.
Air temperature
Output derated in the
range +40 … +50 °C
(+104 … +122 °F).
76 Technical data
Summary of Contents for ACS880-607 Series
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 607 3 phase brake units Hardware manual ...
Page 2: ......
Page 4: ......
Page 8: ...8 ...
Page 12: ...12 ...
Page 30: ...30 ...
Page 32: ...32 ...
Page 36: ...36 ...
Page 44: ...44 ...
Page 54: ...54 ...
Page 62: ...62 ...
Page 66: ...66 Maintenance ...
Page 82: ...Dimension drawing bottom exit 82 Dimension drawings ...
Page 83: ...Dimension drawings 83 ...
Page 84: ...Dimension drawing top exit 84 Dimension drawings ...
Page 85: ... Dimension drawings 85 ...
Page 86: ......