BCU-x2
XD2D
XD2D
XD2D
1
2
3
4
B
A
BGND
SHIEL
D
1
2
3
4
B
A
BGND
SHIEL
D
1
2
3
4
B
A
BGND
SHIEL
D
Termination ON
Termination ON
Termination OFF
The X485 connector
The X485 provides a connection for optional CIO-01 I/O module. The following diagram
shows the wiring for the CIO module.
BCU
CIO
CIO
X485
B
A
BGND
SHIELD
X485
B
A
GND
SHIELD
X485
B
A
GND
SHIELD
Safe torque off (XSTO, XSTO OUT)
Note:
The XSTO input only acts as a true Safe torque off input on the inverter control unit.
De-energizing the IN1 and/or IN2 terminals of other units (supply, DC/DC converter, or brake
unit) will stop the unit but not constitute a true safety function.
FSO-xx safety functions module connection (X12)
See the user manual of the FSO-xx module. Note that the FSO-xx safety functions module
is not in use in supply (or DC/DC converter or brake) units.
SDHC memory card slot
The BCU-x2 has an on-board data logger that collects real-time data from the power modules
to help fault tracing and analysis. The data is stored onto the SDHC memory card inserted
into the SD CARD slot and can be analyzed by ABB service personnel.
56 Control units of the drive
Summary of Contents for ACS880-1607LC
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 1607LC DC DC converter units Hardware manual ...
Page 2: ......
Page 4: ......
Page 12: ...12 ...
Page 32: ...32 ...
Page 38: ...38 ...
Page 60: ...60 ...
Page 80: ...80 ...
Page 90: ...90 ...
Page 102: ...Unit with 1 R8i converter module 102 Dimension drawings ...
Page 103: ...Dimension drawings 103 ...
Page 104: ...Location and size of energy storage connection terminals 104 Dimension drawings ...