Reconnecting the DC/DC converter with DC
switch/disconnector
Tasks
Safety
WARNING!
Obey the safety instructions during the start-up procedure. See
Safety instructions for
ACS880 liquid-cooled multidrive cabinets and modules
(3AXD50000048633 [English]).
If you ignore the safety instructions, injury or death, or damage to the equipment can
occur.
If you are not a qualified electrician, do not do installation or maintenance work.
Reconnecting the DC/DC converter
After you have finished the work inside the converter cubicle, reinstall any shrouds, and close the door.
Reconnect the DC/DC converter and energy storage. See:
•
Connecting voltage to the drive and converter control unit (page 65)
•
Charging the DC/DC converter and connecting voltage to the converter (page 65)
and
•
Connecting the energy storage to the DC/DC converter (page 66)
Starting the DC/DC converter
Change the control panel to local mode (loc/rem key). Set parameter
120.19 Enable start signal
to
value
On
. Press the control panel Start key.
If you need information on the use of the control panel, see
ACX-AP-x assistant control panels user's
manual
(3AUA0000085685 [English]). See also
Drive composer start-up and maintenance PC tool
user's manual
(3AUA0000094606 [English]).
68 Start-up
Summary of Contents for ACS880-1607LC
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 1607LC DC DC converter units Hardware manual ...
Page 2: ......
Page 4: ......
Page 12: ...12 ...
Page 32: ...32 ...
Page 38: ...38 ...
Page 60: ...60 ...
Page 80: ...80 ...
Page 90: ...90 ...
Page 102: ...Unit with 1 R8i converter module 102 Dimension drawings ...
Page 103: ...Dimension drawings 103 ...
Page 104: ...Location and size of energy storage connection terminals 104 Dimension drawings ...