Tasks
Connecting the energy storage to the DC/DC converter
Set parameter
120.12 Run enable 1
to
Off
. This makes sure that the DC/DC converter does not start
automatically or unexpectedly after you connect the energy storage.
Switch the control panel to local control mode.
Make sure that the energy storage voltage is below the drive DC link voltage.
WARNING!
Do not close the energy storage disconnecting device if the DC/DC converter is not connected
to the drive DC link or not ready to use.
Close the energy storage disconnecting device (customer or system integrator-installed device). The
load disconnected indicator [P13.x] goes out.
Close the energy storage protective circuit breaker (customer or system integrator-installed device).
Testing the DC/DC converter operation
Set parameter
120.12 Run enable 1
to
On
.
Set parameter
122.01 User Power ref
to 0 A.
Set current limits to low values, for example,
•
130.119 Minimum current
to -50 A.
•
130.120 Maximum current
to 50 A.
Press the control panel Start key to start the converter. After start, increase slowly the value of para-
meter
122.01 User Power ref
.
Check the following signals:
•
102.01 DC voltage
•
102.02 ES voltage used
•
102.08 Total current
•
102.11 Modulation index %
•
130.101 DDC limit word 1
.
Press the control panel Stop key to stop the converter.
66 Start-up
Summary of Contents for ACS880-1607LC
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 1607LC DC DC converter units Hardware manual ...
Page 2: ......
Page 4: ......
Page 12: ...12 ...
Page 32: ...32 ...
Page 38: ...38 ...
Page 60: ...60 ...
Page 80: ...80 ...
Page 90: ...90 ...
Page 102: ...Unit with 1 R8i converter module 102 Dimension drawings ...
Page 103: ...Dimension drawings 103 ...
Page 104: ...Location and size of energy storage connection terminals 104 Dimension drawings ...