Installation
48
Power cable connection diagram
INPUT
OUTPUT
U1
V1
W1
3
~
Motor
U1 V1 W1
1)
U2 V2 W2
UDC+
R+
UDC
-
R
-
L1
L2
L3
(PE)
(PE)
PE
2)
3)
Drive module
PE
* For alternatives, see
Planning the electrical
installation:
Optional brake
resistor
*
Grounding of the motor cable shield at the motor end
For minimum radio frequency interference:
• ground the cable shield 360 degrees at the lead-through of
the motor terminal box
• or ground the cable by twisting the shield as follows:
flattened width > 1/5 · length.
360 degrees grounding
Conductive gaskets
a
b
b > 1/5 · a
1), 2)
If shielded cable is used (not required but
recommended) and the conductivity of the shield is
< 50 % of the conductivity of the phase conductor,
use a separate PE cable (1) or a cable with a
grounding conductor (2).
Ground the other end of the input cable shield or PE
conductor at the distribution board.
3) Use a separate grounding cable if the conductivity of
the cable shield is < 50 % of the conductivity of the
phase conductor and there is no symmetrically
constructed grounding conductor in the cable (see
Planning the electrical installation
).
Note:
If there is a symmetrically constructed grounding
conductor in the motor cable in addition to the
conductive shield, connect the grounding conductor to
the grounding terminal at the drive and motor ends.
Do not use an asymmetrically constructed motor cable.
Connecting its fourth conductor at the motor end
increases bearing currents and causes extra wear.
Summary of Contents for ACS800-02
Page 1: ...ACS800 Hardware Manual ACS800 02 Drives 45 to 500 kW ACS800 U2 Drives 60 to 600 HP ...
Page 4: ......
Page 10: ...Safety instructions 10 ...
Page 20: ...About this manual 20 ...
Page 26: ...The ACS800 02 U2 26 ...
Page 42: ...Planning the electrical installation 42 ...
Page 76: ...Installation checklist 76 ...
Page 106: ...Technical data 106 ...
Page 108: ...Dimensional drawings 108 Frame size R7 US gland conduit plate 64579746 H ...
Page 109: ...Dimensional drawings 109 Frame size R8 3AFE 64564161 D US gland conduit plate ...
Page 110: ...Dimensional drawings 110 Frame size R7 with enclosure extension bottom entry 64625942 1 2 B ...
Page 111: ...Dimensional drawings 111 64625942 2 2 C ...
Page 112: ...Dimensional drawings 112 Frame size R7 with enclosure extension top entry 64626264 1 2 C ...
Page 113: ...Dimensional drawings 113 64626264 2 2 C ...
Page 115: ...Dimensional drawings 115 3AFE 64626388 2 2 B ...
Page 116: ...Dimensional drawings 116 Frame size R8 with enclosure extension top entry 3AFE 64626370 1 2 C ...
Page 117: ...Dimensional drawings 117 3AFE 64626370 2 2 C ...
Page 118: ...Dimensional drawings 118 ...
Page 127: ......