Motor control and I/O board (RMIO)
71
External control connections (US)
External control cable connections to the RMIO board for the ACS800 Standard
Application Program (Factory Macro US version) are shown below. For external
control connections of other application macros and programs, see the appropriate
Firmware Manual
.
X2*
RMIO
X20
X20
1
1
VREF-
Reference voltage -10 VDC, 1 kohm <
R
L
<
10 kohm
2
2
AGND
X21
X21
1
1
VREF+ Reference voltage 10 VDC, 1 kohm <
R
L
<
10 kohm
2
2
AGND
3
3
AI1+
Speed reference 0(2) ... 10 V,
R
in
>
200 kohm
4
4
AI1-
5
5
AI2+
By default, not in use. 0(4) ... 20 mA
, R
in
=
100 ohm
6
6
AI2-
7
7
AI3+
By default, not in use. 0(4) ... 20 mA
, R
in
=
100 ohm
8
8
AI3-
9
9
AO1+
Motor speed 0(4)...20 mA 0...motor nom.
speed,
R
L
< 700 ohm
10
10
AO1-
11
11
AO2+
Output current 0(4)...20 mA 0...motor
nom. current,
R
L
< 700 ohm
12
12
AO2-
X22
X22
1
1
DI1
Start (
)
2
2
DI2
Stop (
)
3
3
DI3
Forward/Reverse
1)
4
4
DI4
Acceleration & deceleration select
2)
5
5
DI5
Constant speed select
3)
6
6
DI6
Constant speed select
3)
7
7
+24VD +24 VDC max. 100 mA
8
8
+24VD
9
9
DGND1 Digital ground
10
10
DGND2 Digital ground
11
11
DIIL
Start interlock (0 = stop)
4)
X23
X23
1
1
+24V
Auxiliary voltage output, non-isolated,
24 VDC 250 mA
2
2
GND
X25
X25
1
1
RO1
Relay output 1: ready
2
2
RO1
3
3
RO1
X26
X26
1
1
RO2
Relay output 2: running
2
2
RO2
3
3
RO2
X27
X27
1
1
RO3
Relay output 3: fault (-1)
2
2
RO3
3
3
RO3
=
=
Fault
A
rpm
RMIO
Terminal block size:
cables 0.3 to 3.3 mm
2
(22 to 12 AWG)
Tightening torque:
0.2 to 0.4 Nm (0.2 to 0.3 lbf ft)
* optional terminal block in ACS800-U2
and ACS800-U7
1)
Only effective if par. 10.03 is set to
REQUEST by the user.
2)
0 = open, 1 = closed
3)
See par. group 12 CONSTANT
SPEEDS.
4)
See parameter 21.09 START INTRL
FUNC.
DI4 Ramp times according to
0
parameters 22.02 and 22.03
1
parameters 22.04 and 22.05
DI5 DI6 Operation
0
0
Set speed through AI1
1
0
Constant speed 1
0
1
Constant speed 2
1
1
Constant speed 3
Summary of Contents for ACS800-02
Page 1: ...ACS800 Hardware Manual ACS800 02 Drives 45 to 500 kW ACS800 U2 Drives 60 to 600 HP ...
Page 4: ......
Page 10: ...Safety instructions 10 ...
Page 20: ...About this manual 20 ...
Page 26: ...The ACS800 02 U2 26 ...
Page 42: ...Planning the electrical installation 42 ...
Page 76: ...Installation checklist 76 ...
Page 106: ...Technical data 106 ...
Page 108: ...Dimensional drawings 108 Frame size R7 US gland conduit plate 64579746 H ...
Page 109: ...Dimensional drawings 109 Frame size R8 3AFE 64564161 D US gland conduit plate ...
Page 110: ...Dimensional drawings 110 Frame size R7 with enclosure extension bottom entry 64625942 1 2 B ...
Page 111: ...Dimensional drawings 111 64625942 2 2 C ...
Page 112: ...Dimensional drawings 112 Frame size R7 with enclosure extension top entry 64626264 1 2 C ...
Page 113: ...Dimensional drawings 113 64626264 2 2 C ...
Page 115: ...Dimensional drawings 115 3AFE 64626388 2 2 B ...
Page 116: ...Dimensional drawings 116 Frame size R8 with enclosure extension top entry 3AFE 64626370 1 2 C ...
Page 117: ...Dimensional drawings 117 3AFE 64626370 2 2 C ...
Page 118: ...Dimensional drawings 118 ...
Page 127: ......