Technical data
88
1)
50 % overload is available for one minute every 5 minutes if ambient temperature is less than 25 °C.
If ambient temperature is 40 °C, max. available overload is 37 %.
2)
50 % overload is available for one minute every 5 minutes if ambient temperature is less than 30 °C.
If ambient temperature is 40 °C, max. available overload is 40 %.
3)
50 % overload is available one minute every 5 minutes if ambient temperature is less than 20 °C. If
ambient temperature is 40 °C, max. available overload is 30 %.
4)
50 % overload is available one minute every 5 minutes if ambient temperature is less than 35 °C. If
ambient temperature is 40 °C, max. available overload is 45 %.
Symbols
Sizing
The current ratings are the same regardless of the supply voltage within one voltage range. To achieve
the rated motor power given in the table, the rated current of the drive must be higher than or equal to
the rated motor current.
Note 1:
The maximum allowed motor shaft power is limited to 1.5 ·
P
hd
.
If the limit is exceeded, motor
torque and current are automatically restricted. The function protects the input bridge of the drive
against overload.
Note 2:
The ratings apply in ambient temperature of 40 °C (104 °F). In lower temperatures the ratings
are higher (except
I
max
).
Note 3:
Use the DriveSize PC tool for a more accurate dimensioning if the ambient temperature is
below 40 °C (104 °F) or the drive is loaded cyclically.
Nominal ratings
I
cont.max
continuous rms output current. No overload capability at 40 °C.
I
max
maximum output current. Available for 10 s at start, otherwise as long as allowed by drive
temperature.
Typical ratings:
No-overload use
P
cont.max
typical motor power. The power ratings apply to most IEC 34 motors at the nominal voltage,
230 V, 400 V or 500 V.
Light-overload use
(10 % overload capability)
I
2N
continuous rms current. 10 % overload is allowed for one minute every 5 minutes.
P
N
typical motor power. The power ratings apply to most IEC 34 motors at the nominal voltage,
230 V, 400 V or 500 V.
Heavy-duty use
(50 % overload capability)
I
2hd
continuous rms current. 50 % overload is allowed for one minute every 5 minutes.
P
hd
typical motor power. The power ratings apply to most IEC 34 motors at the nominal voltage,
230 V, 400 V or 500 V.
Summary of Contents for ACS800-02
Page 1: ...ACS800 Hardware Manual ACS800 02 Drives 45 to 500 kW ACS800 U2 Drives 60 to 600 HP ...
Page 4: ......
Page 10: ...Safety instructions 10 ...
Page 20: ...About this manual 20 ...
Page 26: ...The ACS800 02 U2 26 ...
Page 42: ...Planning the electrical installation 42 ...
Page 76: ...Installation checklist 76 ...
Page 106: ...Technical data 106 ...
Page 108: ...Dimensional drawings 108 Frame size R7 US gland conduit plate 64579746 H ...
Page 109: ...Dimensional drawings 109 Frame size R8 3AFE 64564161 D US gland conduit plate ...
Page 110: ...Dimensional drawings 110 Frame size R7 with enclosure extension bottom entry 64625942 1 2 B ...
Page 111: ...Dimensional drawings 111 64625942 2 2 C ...
Page 112: ...Dimensional drawings 112 Frame size R7 with enclosure extension top entry 64626264 1 2 C ...
Page 113: ...Dimensional drawings 113 64626264 2 2 C ...
Page 115: ...Dimensional drawings 115 3AFE 64626388 2 2 B ...
Page 116: ...Dimensional drawings 116 Frame size R8 with enclosure extension top entry 3AFE 64626370 1 2 C ...
Page 117: ...Dimensional drawings 117 3AFE 64626370 2 2 C ...
Page 118: ...Dimensional drawings 118 ...
Page 127: ......