ADDED:
Changing internal overtemperature supervision from DI6 to another digital input
By default, digital input DI6 is used for the internal overtemperature supervision of the
drive cabinet. If it is required to use DI6 for an other purpose, change the overtemperature
supervision wiring from DI6 to another free digital input either on the control unit or on the
CMOD-01 multifunction extension module. Active the overtemperature supervision in the
new digital input with these parameter settings:
1. Select the correct digital input from parameter
31.01 External event 1 source
.
2. Check that parameter
31.02 External event 1 type
is set to Fault = 0.
For more information, see the firmware manual.
WARNING!
Always connect the internal overtemperature supervision of the drive
cabinet to a free digital input or CMOD-01 multifunction extension module if
disconnected from digital input DI6. Activate the change. Disconnection of
overtemperature supervision leads to overtemperature and can damage the drive.
PNP configuration for digital inputs (DIGITAL IN)
CHANGED:
Note!
By default, digital input DI6 is used for the internal overtemperature supervision of
the cabinet. If it needs to be changed, see section
Changing internal overtemperature supervision
from DI6 to another digital input
.
X504:10
X504:18
+24 V DC
0 V DC
PNP connection (source)
10
+24V
11
DGND
12
DCOM
13
DI1
14
DI2
15
DI3
16
DI4
17
DI5
18
DI6
X504:18
X504:10
10
+24V
11
DGND
12
DCOM
13
DI1
14
DI2
15
DI3
16
DI4
17
DI5
18
DI6
PNP connection (source)
In24 V power supply
Ex24 V power supply
Summary of Contents for ACS580-07-0495A-4
Page 1: ...ABB general purpose drives Hardware manual ACS580 07 drives 250 to 500 kW ...
Page 4: ......
Page 8: ...4 Update notice ...
Page 16: ...12 ...
Page 24: ...20 Safety instructions ...
Page 42: ...38 Operation principle and hardware description ...
Page 74: ...70 Electrical installation PE PE 8 PE 13 11 7 8 12 13 ...
Page 82: ...78 Electrical installation ...
Page 102: ...98 Fault tracing ...
Page 114: ...110 Maintenance R10 and R11 4 5 2 7 6 3 8 ...
Page 115: ...Maintenance 111 R10 and R11 9 10 ...
Page 116: ...112 Maintenance R10 and R11 11 ...
Page 117: ...Maintenance 113 R10 and R11 12b 12a ...
Page 118: ...114 Maintenance R10 and R11 R10 and R11 17 14 13 R11 15 16 ...
Page 134: ...130 Technical data ...
Page 137: ...Dimension drawings 133 13 Dimension drawings Example dimension drawings are shown below ...
Page 138: ...134 Dimension drawings Frames R10 and R11 IP42 ...
Page 139: ...Dimension drawings 135 Frames R10 and R11 IP54 option B055 ...
Page 140: ...136 Dimension drawings ...
Page 152: ...148 Safe torque off function ...
Page 174: ...Contact us www abb com drives www abb com drivespartners 3AXD50000032622 Rev A EN 2016 03 16 ...