84 Control unit
NPN configuration for digital inputs (DIGITAL IN)
Internal and ex24 V power supply connections for NPN configuration are shown in
the figure below.
Connection for obtaining 0…10 V from analog output 2 (ANALOG IN/OUT)
To obtain 0…10 V from analog output AO2, connect a 500 ohm resistor (or two 1 kohm
resistors in parallel) between analog output AO2 and analog common ground AGND.
Examples are shown in the figure below.
In24 V power supply
Ex24 V power supply
10
+24V
11
DGND
12
DCOM
13
DI1
14
DI2
15
DI3
16
DI4
17
DI5
18
DI6
NPN connection (sink)
NPN connection (sink)
10
+24V
11
DGND
12
DCOM
13
DI1
14
DI2
15
DI3
16
DI4
17
DI5
18
DI6
0 V DC
+24 V DC
8 AO2
Analog output 2. Default output 0…20 mA.
9 AGND
Analog common ground. Internally connected to chassis
through a 2 Mohm resistor.
500 ohm
8 AO2
Analog output 2. Default output 0…20 mA.
9 AGND
Analog common ground. Internally connected to chassis
through a 2 Mohm resistor.
1 kohm
1 kohm
0…
10
V
0…
10
V
Summary of Contents for ACS580-07-0495A-4
Page 1: ...ABB general purpose drives Hardware manual ACS580 07 drives 250 to 500 kW ...
Page 4: ......
Page 8: ...4 Update notice ...
Page 16: ...12 ...
Page 24: ...20 Safety instructions ...
Page 42: ...38 Operation principle and hardware description ...
Page 74: ...70 Electrical installation PE PE 8 PE 13 11 7 8 12 13 ...
Page 82: ...78 Electrical installation ...
Page 102: ...98 Fault tracing ...
Page 114: ...110 Maintenance R10 and R11 4 5 2 7 6 3 8 ...
Page 115: ...Maintenance 111 R10 and R11 9 10 ...
Page 116: ...112 Maintenance R10 and R11 11 ...
Page 117: ...Maintenance 113 R10 and R11 12b 12a ...
Page 118: ...114 Maintenance R10 and R11 R10 and R11 17 14 13 R11 15 16 ...
Page 134: ...130 Technical data ...
Page 137: ...Dimension drawings 133 13 Dimension drawings Example dimension drawings are shown below ...
Page 138: ...134 Dimension drawings Frames R10 and R11 IP42 ...
Page 139: ...Dimension drawings 135 Frames R10 and R11 IP54 option B055 ...
Page 140: ...136 Dimension drawings ...
Page 152: ...148 Safe torque off function ...
Page 174: ...Contact us www abb com drives www abb com drivespartners 3AXD50000032622 Rev A EN 2016 03 16 ...