ABB VFD SUPPLEMENTAL MANUAL  

1.800.627.4499

2

PLANNING 

YOUR INSTALLATION

ABOUT ABB VFDS 

PRODUCT INFO

ABB ACS320 VFDs are generally supplied in indoor ERVs and ABB N831 VFDs in roof top ERVs. 
Both models have built in BACnet

®

 building communication protocol and the N831 also has 

low ambient fi rmware that extends the lower starting temperature limit to -25°F.

FOR COMPLETE ERV INSTALLATION YOU WILL ALSO NEED:

• 

Standard Installation and Operation Manual for the ERV

 – physical installation and duct connection, 

maintenance procedures, etc.

• 

Supplemental Wiring Schematic Manual

 – complete unit wiring diagrams. 

• 

User’s Manual ACS320 Drives or Users Manual ACS355 Drives

 – ABB’s user’s/installer’s manual. 

More detailed information is available online in the Document Library at www.abb.com/drives.

1.  Before servicing or cleaning the unit, switch 

power off at disconnect switch or service panel 
and lock-out/tag-out to prevent power from 
being switched on accidentally. More than one 
disconnect switch may be required to 
de-energize the equipment for servicing.

2.  This installation manual shows the suggested 

installation method. Additional measures may 
be required by local codes and standards.

3.  Installation work and electrical wiring must be 

done by qualifi ed professional(s) in accordance 
with all applicable codes, standards and 
licensing requirements.

4.  Any structural alterations necessary for 

installation must comply with all applicable 
building, health, and safety code requirements.  

5.  This unit must be grounded.
6.  Use the unit only in the manner intended by the 

manufacturer. If you have questions, contact 
the manufacturer.

7.  When cutting or drilling into unit, wall or 

ceiling, do not damage electrical wiring and 
other hidden utilities.

8.  Do not re-wire the VFD(s) to control more than 

one motor per VFD.

9.  Do not operate the motors in this unit above 

the motor’s rated full load amps (FLA) as 
indicated on the unit’s nameplate.

RISK OF FIRE, ELECTRIC SHOCK, OR INJURY. OBSERVE ALL CODES AND THE FOLLOWING:

WARNING

NOTE: 

VFD(s) in this unit can be operated in many ways. This Manual provides only an outline of common methods. 

DO NOT OPERATE VFD IN CONDITIONS OUTSIDE OF TEMPERATURE LIMITS.

 The manufacturer’s normal 

ambient temperature limits for ACS320 VFDs are 14°F to 122°F.   RenewAire has worked with the manufacturer 
to implement low-ambient-start fi rmware for the N831 that extends the lower temperature 
limit for starting the VFD down to -25°F, which has been validated by manufacturer and RenewAire testing. 
The manufacturer recommends that the VFD not be operated for prolonged periods at temperatures below 
14°F to ensure longevity of the VFD. RenewAire commercial ERVs are VFD ready, in extreme climates 
consider fi eld installing VFDs in a climate controlled indoor electrical cabinet.

WARNING

Summary of Contents for ACS320 series

Page 1: ...FD KEYPADS IN E BOX SUPPLEMENTAL MANUAL FACTORY INSTALLED ABB VARIABLE FREQUENCY DRIVES VFD IN RENEWAIRE ERV VENTILATORS RENEWAIRE COM TABLE OF CONTENTS Product info 2 Installation 3 9 Operation 10 16...

Page 2: ...al s in accordance with all applicable codes standards and licensing requirements 4 Any structural alterations necessary for installation must comply with all applicable building health and safety cod...

Page 3: ...w the leader s speed or at a scaled speed The VFD s are pre programmed at the factory so only a few parameters need change for a speci c installation CONNECTING EXTERNAL CONTROLS If this ERV is equipp...

Page 4: ...und on the Internet at www abb com drives and selecting Sales Support and Service Network Softkey Auto OFF Hand Softkey Help Key Up Down Buttons The function of each Softkey changes and is shown just...

Page 5: ...ected directly to the VFD See Fig 2 3 SPEED SIGNAL CONNECTIONS Any SPEED Signal connections are made directly to the VFD see Figures 4 6 7 The VFDs can accept 4 20mA or 0 10vdc analog control signals...

Page 6: ...9 10 11 12 15 8 7 6 5 4 3 2 1 AGND A01 AGND AI2 10V AGND AI1 SCR VFD FA 9 10 11 12 15 8 7 6 5 4 3 2 1 AGND A01 AGND AI2 10V AGND AI1 SCR VFD EA 17 19 PARAMETER SETTINGS FA VFD Parameter Setting Param...

Page 7: ...Speed Signal to the EA VFD Use shielded cable and ground the shield to Terminal 1 on either VFD 1 1 9 1 6 5 9 XVLQJ YGF 1 1 9 1 6 5 9 XVLQJ P RQQHFWLRQV IRU YGF RQWUROOHU 6HW XPSHU RU VZLWFK WR 27720...

Page 8: ...in this example since it is controlled as a Follower If it is desired that the VFDs should shut off when CO2 levels drop below a setpoint connect the Normally Open contacts of the CO2 controller term...

Page 9: ...auspices of the American Society of Heating Refrigerating and Air Conditioning Engineers ASHRAE BACnet is an American national standard a European standard a national standard in more than 30 countrie...

Page 10: ...ange the VFD parameters as required for the speci c controls system see Control Connections and VFD Parameters below for examples see also the ABB Manuals Press the AUTO switch on the keypad 230V Powe...

Page 11: ...eter 3 Press the SAVE softkey to set the Parameter to the selected value TO VIEW ONLY CHANGED VFD PARAMETERS 1 If EXIT is displayed above the left softkey press softkey repeatedly until MENU appears a...

Page 12: ...or scaling and offsetting the input to the VFD output 1302 MAXIMUM AI1 100 100 Sets maximum value for analog input Used for scaling and offsetting the input to the VFD output 1304 MINIMUM AI2 20 1 20...

Page 13: ...abb com drives SUMMARY TABLE OF COMMONLY USED PARAMETERS CONT NOTE Parameters not listed in this Table are shipped at ABB s default settings for the HVAC Application Macro Name Selection ABB HVAC Defa...

Page 14: ...NSE LEVEL is the level of measurement of indoor air quality or occupancy at which the ERV should be operating at the Design Maximum Supply Air ow Do not change PARAMETER 2003 MAX CURRENT from RenewAir...

Page 15: ...he Maximum Response Level The engineer wants the ERV to Run at a minimum of 700 CFM regardless of CO2 levels in order to control the level of indoor air pollutants generated by the furnishings Start t...

Page 16: ...value of the analog signal from the controller when CO2 600ppm 6 Set the parameters that will scale the response of the VFD to the inputs from the CO2 controller Set Parameter 1301 MINIMUM AI 1 to 55...