SETTINGS

OPERATION

 

 

VFD PARAMETER OVERVIEW

“VFD Parameters” are instructions that the Variable Frequency Drives follow. They can be adjusted by 
using the keypads on the VFDs. In some control confi gurations, they will need to be changed from the 
settings as shipped in the unit to interface with your control system. 

To view the VFD’s Parameters from the keypad, press the MENU softkey. Press up/down arrows to highlight 
PARAMETERS, then select it by pressing the ENTER softkey.

TO VIEW ALL VFD PARAMETERS

VFD must be powered up – something will be showing on the LED display.

1.  If EXIT is displayed above the left softkey, press softkey repeatedly until MENU appears above the right softkey.
2. Press the MENU softkey.
3. Use the UP/DOWN arrows to scroll the display until PARAMETERS is selected, then press the ENTER softkey.
4. You will see a numbered list of Parameter “groups” – those numbers are the fi rst two digits of the 

Parameters in each group.

5. Press the SEL softkey to view all the Parameters in each Group. Use the UP/DOWN buttons to scroll 

through the parameters. As each Parameter is selected, its value will be displayed.

TO CHANGE VFD PARAMETERS (WHEN 
PARAMETERS ARE UNLOCKED)

1. Select the Parameter you want to edit (see above). 

Press the EDIT softkey.

2. Use the UP/DOWN arrows to scroll through the 

available settings for that Parameter.

3. Press the SAVE softkey to set the Parameter to 

the selected value.

TO VIEW ONLY CHANGED VFD PARAMETERS

1. If EXIT is displayed above the left softkey, press 

softkey repeatedly until MENU appears above the 
right softkey.

2. Press the MENU softkey.
3. Use the UP/DOWN arrows to scroll the display 

until CHANGED PAR is selected, then press the 
ENTER softkey.

4. All Parameters that have been changed from 

the HVAC Application Macro default values are 
displayed. Use the UP/DOWN buttons to view 
them all.

To unlock all Parameters if Parameter 1602 
reads LOCKED:

1. Select Parameter 1603 PASS CODE: press 

EDIT softkey.

2. Use the UP / DOWN buttons to scroll to 358: press 

SAVE softkey (the entry will automatically revert 
back to 0); press EXIT softkey.

3. Scroll up to Parameter 1602 PARAMETER LOCK 

which reads LOCKED; press EDIT softkey.

4. Scroll to OPEN; press SAVE softkey; press 

EXIT softkey

Parameters are now unlocked. You can view and 
change them.

To lock Parameters after changes are made if 
Parameter 1602 reads OPEN:

1. 

Select Parameter 1603 PASS CODE: press 
EDIT softkey.

2. Use the UP / DOWN buttons to scroll to 358: press 

SAVE softkey (the entry will automatically revert 
back to 0); press EXIT softkey.

3. Scroll up to Parameter 1602 PARAMETER LOCK 

which reads OPEN; press EDIT softkey.

4. Scroll to LOCKED; press SAVE softkey; press 

EXIT softkey. 

Parameters are now locked. You can view them but 
you cannot change them.

TO LOCK OR UNLOCK PARAMETERS

VFDs are shipped locked to prevent accidental changes to parameter settings. If changes to factory parameter 
settings are desired, the VFD will need to be unlocked for editing the settings. 

Summary of Contents for ACS320 series

Page 1: ...FD KEYPADS IN E BOX SUPPLEMENTAL MANUAL FACTORY INSTALLED ABB VARIABLE FREQUENCY DRIVES VFD IN RENEWAIRE ERV VENTILATORS RENEWAIRE COM TABLE OF CONTENTS Product info 2 Installation 3 9 Operation 10 16...

Page 2: ...al s in accordance with all applicable codes standards and licensing requirements 4 Any structural alterations necessary for installation must comply with all applicable building health and safety cod...

Page 3: ...w the leader s speed or at a scaled speed The VFD s are pre programmed at the factory so only a few parameters need change for a speci c installation CONNECTING EXTERNAL CONTROLS If this ERV is equipp...

Page 4: ...und on the Internet at www abb com drives and selecting Sales Support and Service Network Softkey Auto OFF Hand Softkey Help Key Up Down Buttons The function of each Softkey changes and is shown just...

Page 5: ...ected directly to the VFD See Fig 2 3 SPEED SIGNAL CONNECTIONS Any SPEED Signal connections are made directly to the VFD see Figures 4 6 7 The VFDs can accept 4 20mA or 0 10vdc analog control signals...

Page 6: ...9 10 11 12 15 8 7 6 5 4 3 2 1 AGND A01 AGND AI2 10V AGND AI1 SCR VFD FA 9 10 11 12 15 8 7 6 5 4 3 2 1 AGND A01 AGND AI2 10V AGND AI1 SCR VFD EA 17 19 PARAMETER SETTINGS FA VFD Parameter Setting Param...

Page 7: ...Speed Signal to the EA VFD Use shielded cable and ground the shield to Terminal 1 on either VFD 1 1 9 1 6 5 9 XVLQJ YGF 1 1 9 1 6 5 9 XVLQJ P RQQHFWLRQV IRU YGF RQWUROOHU 6HW XPSHU RU VZLWFK WR 27720...

Page 8: ...in this example since it is controlled as a Follower If it is desired that the VFDs should shut off when CO2 levels drop below a setpoint connect the Normally Open contacts of the CO2 controller term...

Page 9: ...auspices of the American Society of Heating Refrigerating and Air Conditioning Engineers ASHRAE BACnet is an American national standard a European standard a national standard in more than 30 countrie...

Page 10: ...ange the VFD parameters as required for the speci c controls system see Control Connections and VFD Parameters below for examples see also the ABB Manuals Press the AUTO switch on the keypad 230V Powe...

Page 11: ...eter 3 Press the SAVE softkey to set the Parameter to the selected value TO VIEW ONLY CHANGED VFD PARAMETERS 1 If EXIT is displayed above the left softkey press softkey repeatedly until MENU appears a...

Page 12: ...or scaling and offsetting the input to the VFD output 1302 MAXIMUM AI1 100 100 Sets maximum value for analog input Used for scaling and offsetting the input to the VFD output 1304 MINIMUM AI2 20 1 20...

Page 13: ...abb com drives SUMMARY TABLE OF COMMONLY USED PARAMETERS CONT NOTE Parameters not listed in this Table are shipped at ABB s default settings for the HVAC Application Macro Name Selection ABB HVAC Defa...

Page 14: ...NSE LEVEL is the level of measurement of indoor air quality or occupancy at which the ERV should be operating at the Design Maximum Supply Air ow Do not change PARAMETER 2003 MAX CURRENT from RenewAir...

Page 15: ...he Maximum Response Level The engineer wants the ERV to Run at a minimum of 700 CFM regardless of CO2 levels in order to control the level of indoor air pollutants generated by the furnishings Start t...

Page 16: ...value of the analog signal from the controller when CO2 600ppm 6 Set the parameters that will scale the response of the VFD to the inputs from the CO2 controller Set Parameter 1301 MINIMUM AI 1 to 55...

Reviews: