background image

ABB VARIABLE FREQUENCY DRIVES

13

1.800.627.4499  

ABB VFD SUPPLEMENTAL MANUAL  

RENEWAIRE.COM 

SETTINGS

OPERATION

 

 

TO RESET VFD PARAMETERS TO FACTORY SETTINGS USING KEYPAD 

The VFD will need to be unlocked as described on page 11 to reset Parameters to RenewAire factory or 
ABB defaults.

To return to RenewAire’s defaults, select parameter 9902 APPLIC MACRO and press EDIT softkey. Scroll 
down to USER 1 LOAD (Not USER 1 SAVE as this will overwrite the factory settings saved under USER 1 in 
the VFD base memory). Press the SAVE softkey.

Alternatively, to return to RenewAire’s defaults, select PAR BACKUP in the keypad menu; scroll to and 
select DOWNLOAD FULL SET (not UPLOAD TO PANEL as this will overwrite the factory settings saved in the 
keypad memory).

To return to ABB’s defaults, select parameter 9902 APPLIC MACRO and press EDIT softkey. Scroll up or 
down to select HVAC DEFAULT. Press the SAVE softkey. If HVAC DEFAULT was displayed without scrolling 
after pressing EDIT in parameter 9902, you will need to scroll up to another macro  numbered 2 through 
15 and press SAVE, then scroll back down to 1=HVAC DEFAULT and press SAVE again to get the settings to 
revert back to the original ABB defaults.

To save an edited parameter set for possible restoration, select parameter 9902 APPLIC MACRO and press 
EDIT softkey. Scroll down to USER 2 SAVE (Not USER 1 SAVE as this will overwrite the factory settings 
saved under USER 1 in the VFD base memory). Press the SAVE softkey. This edited parameter set can now 
be reset using USER 2 LOAD.

The VFD should be relocked as described above after the desired parameter settings are entered to avoid 
further, accidental changes to parameter settings.

NOTE: 

VFD Manufacturer instructions list many other parameters. Copies of the complete manufacturer’s 

instructions for the VFD are shipped with this unit, and are also available on-line in the Document Library 
at www.abb.com/drives.

SUMMARY TABLE OF COMMONLY USED PARAMETERS (CONT.)

NOTE:  

Parameters not listed in this Table are shipped at ABB’s default settings for the HVAC Application Macro.

Name/Selection

ABB HVAC Default 

ACS320/N831

Settings as 

Shipped BY RenewAire

FUNCTION

2202

ACCELER TIME 1

30.0 s

30.0 s

Sets acceleration time.

2203

DECELER TIME 1

30.0 s

30.0 s

Sets deceleration time.  This is ignored when 2102 STOP FUNCTION = COAST.

2607

SWITCH FREQ CONTROL 1=ON/2=ON (LOAD)

1=ON

Selects the control method for the switching frequency.

2609

NOISE SMOOTHING

0=DISABLED

0=DISABLED

Set to 1=enabled to activate the noise smoothing function. Noise smoothing lowers 
peak noise intensity by distributing acoustic motor noise over a range of frequencies.

3007

MOT LOAD CURVE

100%

98% (TYP.)**

CRITICAL PARAMETER. Defi nes motor load curve.

3401*

SIGNAL 1 PARAM

103=OUTPUT FREQUENCY

101=SPEED AND DIR

Sets top line of keypad display to show motor speed in rpm.***

3408*

SIGNAL 2 PARAM

104=CURRENT

104=CURRENT

Sets middle line of keypad display to show motor current in Amps.***

3415*

SIGNAL 3 PARAM

120=AI 1

120=AI 1

Sets bottom line of keypad display to show value of analog signal input.***

* This parameter is not visible in the “short view”. To be able to view all signals and parameters, set parameter 1611 PARAMETER VIEW to 3 (LONG VIEW) on ACS320 VFDs.

** Parameter 2003 is set 125% for motors with 1.15 Service Factor (SF) or higher or otherwise protected and 115% for motors with less than 1.15 SF and otherwise 
unprotected. Parameter 3007 is set 98% for motors wiht 1.15 SF or higher, 90% for motors with less than 1.15 SF and 100% for motors that are otherwise protected.

***   Numerous keypad operating data display options are listed in parameter Group 01.

****  Maximum Frequency set higher in LE units to generally operate motors near 60 Hz or faster resulting in higher motor output HP.

NOTE: 

SPEED-SKIPPING is a function available through Parameters 2501-2507. It allows up to 3 critical speeds to be skipped as the VFD ramps speed up and down. 

If noise problems occur at specifi c frequencies, Speed-Skipping may help. See the VFD manual for details.

Summary of Contents for ACS320 series

Page 1: ...FD KEYPADS IN E BOX SUPPLEMENTAL MANUAL FACTORY INSTALLED ABB VARIABLE FREQUENCY DRIVES VFD IN RENEWAIRE ERV VENTILATORS RENEWAIRE COM TABLE OF CONTENTS Product info 2 Installation 3 9 Operation 10 16...

Page 2: ...al s in accordance with all applicable codes standards and licensing requirements 4 Any structural alterations necessary for installation must comply with all applicable building health and safety cod...

Page 3: ...w the leader s speed or at a scaled speed The VFD s are pre programmed at the factory so only a few parameters need change for a speci c installation CONNECTING EXTERNAL CONTROLS If this ERV is equipp...

Page 4: ...und on the Internet at www abb com drives and selecting Sales Support and Service Network Softkey Auto OFF Hand Softkey Help Key Up Down Buttons The function of each Softkey changes and is shown just...

Page 5: ...ected directly to the VFD See Fig 2 3 SPEED SIGNAL CONNECTIONS Any SPEED Signal connections are made directly to the VFD see Figures 4 6 7 The VFDs can accept 4 20mA or 0 10vdc analog control signals...

Page 6: ...9 10 11 12 15 8 7 6 5 4 3 2 1 AGND A01 AGND AI2 10V AGND AI1 SCR VFD FA 9 10 11 12 15 8 7 6 5 4 3 2 1 AGND A01 AGND AI2 10V AGND AI1 SCR VFD EA 17 19 PARAMETER SETTINGS FA VFD Parameter Setting Param...

Page 7: ...Speed Signal to the EA VFD Use shielded cable and ground the shield to Terminal 1 on either VFD 1 1 9 1 6 5 9 XVLQJ YGF 1 1 9 1 6 5 9 XVLQJ P RQQHFWLRQV IRU YGF RQWUROOHU 6HW XPSHU RU VZLWFK WR 27720...

Page 8: ...in this example since it is controlled as a Follower If it is desired that the VFDs should shut off when CO2 levels drop below a setpoint connect the Normally Open contacts of the CO2 controller term...

Page 9: ...auspices of the American Society of Heating Refrigerating and Air Conditioning Engineers ASHRAE BACnet is an American national standard a European standard a national standard in more than 30 countrie...

Page 10: ...ange the VFD parameters as required for the speci c controls system see Control Connections and VFD Parameters below for examples see also the ABB Manuals Press the AUTO switch on the keypad 230V Powe...

Page 11: ...eter 3 Press the SAVE softkey to set the Parameter to the selected value TO VIEW ONLY CHANGED VFD PARAMETERS 1 If EXIT is displayed above the left softkey press softkey repeatedly until MENU appears a...

Page 12: ...or scaling and offsetting the input to the VFD output 1302 MAXIMUM AI1 100 100 Sets maximum value for analog input Used for scaling and offsetting the input to the VFD output 1304 MINIMUM AI2 20 1 20...

Page 13: ...abb com drives SUMMARY TABLE OF COMMONLY USED PARAMETERS CONT NOTE Parameters not listed in this Table are shipped at ABB s default settings for the HVAC Application Macro Name Selection ABB HVAC Defa...

Page 14: ...NSE LEVEL is the level of measurement of indoor air quality or occupancy at which the ERV should be operating at the Design Maximum Supply Air ow Do not change PARAMETER 2003 MAX CURRENT from RenewAir...

Page 15: ...he Maximum Response Level The engineer wants the ERV to Run at a minimum of 700 CFM regardless of CO2 levels in order to control the level of indoor air pollutants generated by the furnishings Start t...

Page 16: ...value of the analog signal from the controller when CO2 600ppm 6 Set the parameters that will scale the response of the VFD to the inputs from the CO2 controller Set Parameter 1301 MINIMUM AI 1 to 55...