ABB VARIABLE FREQUENCY DRIVES

RENEWAIRE.COM  

ABB VFD SUPPLEMENTAL MANUAL  

1.800.627.4499

12

SETTINGS

OPERATION

Name/Selection

ABB HVAC Default ACS320/

N831

Settings as Shipped By 

RenewAire

FUNCTION

9802

COMMUNICATION
PROTOCOL SELECTION

0=NOT SEL/5=BACnet

0=NOT SEL

Activates the external serial communication and selects the interface. 
Set to 5=BACnet if integrating VFD into BACnet® system.

9902

APPLIC MACRO

HVAC

HVAC

Pressing SAVE softkey when USER 1 LOAD is selected returns the VFD 
to the parameters as shipped from RenewAire. Pressing SAVE softkey 
when HVAC DEFAULT is selected returns the VFD to the ABB defaults.

9905

MOTOR NOM VOLT

VFD rating

Equal to Motor Voltage

Must be set equal to wired motor voltage.

9906

MOTOR NOM CURR

VFD rating

Equal to Motor FLA

Must be set equal to motor nameplate FLA. CRITICAL FOR SAFETY.

9907

MOTOR NOM FREQ

60.0 Hz

60.0 Hz

Must be set 60.0 Hz

9908

MOTOR NOM SPEED

Size Dependent

Set per motor

Usually 1750.

9909

MOTOR NOM POWER

VFD rating

Equal to Motor HP

Must be set to Motor nameplate HP.

1001*

EXT1 COMMANDS

1=DI1

1=DI1

Enables 2-wire start-stop when closing contact between 9 & 12.  
(Jumper req’d between 10&11.)

1103*

REF1 SEL

1=AI1

0=KEYPAD

Selects signal source for external reference REF 1.  
Change to 1=AI1 for operation by an external control signal.

1104*

REF1 MIN

0.0 Hz

0.0 Hz

Sets minimum value for speed reference.  Used for scaling and 
offsetting the input to the VFD output.

1105

REF1 MAX

60.0 Hz

60.0 Hz

Sets maximum value for speed reference.  Used for scaling and 
offsetting the input to the VFD output.

1201*

CONST SPEED SEL

3=DI3

9=DI3,4

Enables three-speed operation at three preset speeds using two 
switches between 9&13 and 9&14.

1202

CONST SPEED 1

6.0 (Hz)

30.0 Hz

Determines preset speed 1.

1203

CONST SPEED 2

12.0 (Hz)

45.0 Hz

Determines preset speed 2.

1204

CONST SPEED 3

18.0 (Hz)

60.0 Hz

Determines preset speed 3.

1301

MINIMUM AI1

20%

20%

Sets minimum value for analog input.  Used for scaling and 
offsetting the input to the VFD output.

1302

MAXIMUM AI1

100%

100%

Sets maximum value for analog input.  Used for scaling and 
offsetting the input to the VFD output.

1304

MINIMUM AI2

20%/1%

20%

Sets minimum value for analog input AI2.

1401

RELAY OUTPUT 1

1=READY

2=RUN

Energizes Relay 1 when drive is running. 
Terminal 17=COM, 18=N.C., 19= N.O.

1501

AO 1 CONTENT SEL

103=OUTPUT FREQ

103=OUTPUT FREQ

Sets the Analog Output of the VFD equal to the Output Frequency 
at which it is driving its Motor.

1502

AO 1 CONTENT MIN 

0.0 Hz

0.0 Hz

Scales the minimum value of the analog output with respect 
to the VFDs Output Frequency.

1503

AO 1 CONTENT MAX

60.0 Hz

60.0 Hz

Scales the maximum value of the analog output with respect 
to the VFDs Output Frequency.

1504

MINIMUM AO 1

4.0 mA

4.0 mA

Sets the minimum current for the Analog Output.

1505

MAXIMUM AO 1

20.0 mA

20.0 mA

Sets the maximum current for the Analog Output.

1602*

PARAMETER LOCK

1=OPEN

0=LOCKED

Allows you to lock or change parameters from the keypad.

1603*

PASS CODE

0

0

Entering pass code 358 allows you to change parameter 1602 once. 
The entry reverts back to 0 automatically.

1607*

PARAM.SAVE

0 = DONE

0 = DONE

Saves parameters to permanent memory

1608*

START ENABLE 1

4=DI4

1=DI1

Enables DI1 as the source of the Start Enable Signal.

1611

PARAMETER VIEW

SHORT VIEW/DEFAULT

LONG VIEW/DEFAULT

(SHORT VIEW) Hides less commonly used parameters

2003*

MAX CURRENT

1.1*I

2N  

/1.8*I

2N

Typically set to 125% motor 
FLA **

CRITICAL PARAMETER.  Defi nes motor protection level.

2007*

MINIMUM FREQ

0.0 Hz

15.0 Hz

Determines minimum frequency of VFD output

2008

MAXIMUM FREQ

60.0 Hz

60.0 Hz HE units
90.0 Hz LE units****

Determines maximum frequency of VFD output

2101*

START FUNCTION

1=AUTO

6=SCAN START

Selects the motor start method.  SCAN START provides a 
frequency-scanning fl ying start, and corrects backwards rotation.

2102

STOP FUNCTION

1=COAST

1=COAST

Sets motor to coast to a halt. Can be set to ramp down to a halt, 
following the deceleration time set at 2203.

SUMMARY TABLE OF COMMONLY USED PARAMETERS

NOTE:  

Parameters not listed in this Table are shipped at ABB’s default settings for the HVAC Application Macro.

Summary of Contents for ACS320 series

Page 1: ...FD KEYPADS IN E BOX SUPPLEMENTAL MANUAL FACTORY INSTALLED ABB VARIABLE FREQUENCY DRIVES VFD IN RENEWAIRE ERV VENTILATORS RENEWAIRE COM TABLE OF CONTENTS Product info 2 Installation 3 9 Operation 10 16...

Page 2: ...al s in accordance with all applicable codes standards and licensing requirements 4 Any structural alterations necessary for installation must comply with all applicable building health and safety cod...

Page 3: ...w the leader s speed or at a scaled speed The VFD s are pre programmed at the factory so only a few parameters need change for a speci c installation CONNECTING EXTERNAL CONTROLS If this ERV is equipp...

Page 4: ...und on the Internet at www abb com drives and selecting Sales Support and Service Network Softkey Auto OFF Hand Softkey Help Key Up Down Buttons The function of each Softkey changes and is shown just...

Page 5: ...ected directly to the VFD See Fig 2 3 SPEED SIGNAL CONNECTIONS Any SPEED Signal connections are made directly to the VFD see Figures 4 6 7 The VFDs can accept 4 20mA or 0 10vdc analog control signals...

Page 6: ...9 10 11 12 15 8 7 6 5 4 3 2 1 AGND A01 AGND AI2 10V AGND AI1 SCR VFD FA 9 10 11 12 15 8 7 6 5 4 3 2 1 AGND A01 AGND AI2 10V AGND AI1 SCR VFD EA 17 19 PARAMETER SETTINGS FA VFD Parameter Setting Param...

Page 7: ...Speed Signal to the EA VFD Use shielded cable and ground the shield to Terminal 1 on either VFD 1 1 9 1 6 5 9 XVLQJ YGF 1 1 9 1 6 5 9 XVLQJ P RQQHFWLRQV IRU YGF RQWUROOHU 6HW XPSHU RU VZLWFK WR 27720...

Page 8: ...in this example since it is controlled as a Follower If it is desired that the VFDs should shut off when CO2 levels drop below a setpoint connect the Normally Open contacts of the CO2 controller term...

Page 9: ...auspices of the American Society of Heating Refrigerating and Air Conditioning Engineers ASHRAE BACnet is an American national standard a European standard a national standard in more than 30 countrie...

Page 10: ...ange the VFD parameters as required for the speci c controls system see Control Connections and VFD Parameters below for examples see also the ABB Manuals Press the AUTO switch on the keypad 230V Powe...

Page 11: ...eter 3 Press the SAVE softkey to set the Parameter to the selected value TO VIEW ONLY CHANGED VFD PARAMETERS 1 If EXIT is displayed above the left softkey press softkey repeatedly until MENU appears a...

Page 12: ...or scaling and offsetting the input to the VFD output 1302 MAXIMUM AI1 100 100 Sets maximum value for analog input Used for scaling and offsetting the input to the VFD output 1304 MINIMUM AI2 20 1 20...

Page 13: ...abb com drives SUMMARY TABLE OF COMMONLY USED PARAMETERS CONT NOTE Parameters not listed in this Table are shipped at ABB s default settings for the HVAC Application Macro Name Selection ABB HVAC Defa...

Page 14: ...NSE LEVEL is the level of measurement of indoor air quality or occupancy at which the ERV should be operating at the Design Maximum Supply Air ow Do not change PARAMETER 2003 MAX CURRENT from RenewAir...

Page 15: ...he Maximum Response Level The engineer wants the ERV to Run at a minimum of 700 CFM regardless of CO2 levels in order to control the level of indoor air pollutants generated by the furnishings Start t...

Page 16: ...value of the analog signal from the controller when CO2 600ppm 6 Set the parameters that will scale the response of the VFD to the inputs from the CO2 controller Set Parameter 1301 MINIMUM AI 1 to 55...

Reviews: