1.  MEASUREMENT RANGE: the range of the values that can be measured by the Controller (e.g. a 

controller set to measure CO2 from 0ppm to 1100ppm).

2

2.  ANALOG SIGNAL TYPE: vdc or mA.

3.  MINIMUM SIGNAL VALUE of the analog signal: e.g. 0vdc or 4mA. This is the signal that the controller 

puts out when it is measuring at the bottom of its measurement range.

4.  MAXIMUM SIGNAL VALUE of the analog signal: e.g. 10vdc, 20mA. This is the signal that the controller 

puts out when it is measuring at the top of its measurement range

5.  SIGNAL RANGE: the difference between the maximum and minimum signal values from the controller. 

In the case of a 0-10vdc controller the Signal Range is 10vdc. In the case of a 4-20mA Controller the 
Signal Range is 16mA.

6.  ACTION LEVEL SIGNAL: the value of the analog signal corresponding to the “Action Level”.

7.  MAXIMUM RESPONSE LEVEL SIGNAL: the value of the analog signal corresponding to the “Maximum 

Response Level”.

The engineer wants the ERV to:
•  Run at a minimum of 700 CFM, regardless of CO2 levels, in order to control the level of indoor air 

pollutants generated by the furnishings.

•  Start to increase airfl ow when CO2 levels rise above 600ppm.

•  As CO2 levels continue to rise, the ERV should increase airfl ow, hitting a maximum of 1500 CFM at 1000 

ppm CO2 level.

The CO2 controller is set up to deliver a linear 4-20mA signal over a measurement range of 0 to 1100ppm.

During the test and balance process, the ERV is found to deliver 700 CFM at 20Hz, and 1500CFM at 50Hz.

THEREFORE:

ACTION LEVEL = 600ppm
MAXIMUM RESPONSE LEVEL = 1000ppm
MAXIMUM SPEED = 50Hz
MINIMUM SPEED = 20Hz
ANALOG SIGNAL TYPE = mA.
MINIMUM SIGNAL VALUE = 4mA
MAXIMUM SIGNAL VALUE = 20mA
SIGNAL RANGE = 16mA
MEASUREMENT RANGE of the controller = 1100ppm

F9 APPLICATION EXAMPLE: CO2 CONTROLLER

2

  This does not mean the range of values that will be measured. For example, a CO2 controller might be set so that it can measure from 0ppm to 1100ppm. The Measurement Range is therefore 

0-1100ppm. In the fi eld the controller might never read a value below 400ppm or above 1000ppm, but this is not the meaning of Measurement Range.

ADDITIONAL JOB INFORMATION NEEDED:

Summary of Contents for ACS320 series

Page 1: ...FD KEYPADS IN E BOX SUPPLEMENTAL MANUAL FACTORY INSTALLED ABB VARIABLE FREQUENCY DRIVES VFD IN RENEWAIRE ERV VENTILATORS RENEWAIRE COM TABLE OF CONTENTS Product info 2 Installation 3 9 Operation 10 16...

Page 2: ...al s in accordance with all applicable codes standards and licensing requirements 4 Any structural alterations necessary for installation must comply with all applicable building health and safety cod...

Page 3: ...w the leader s speed or at a scaled speed The VFD s are pre programmed at the factory so only a few parameters need change for a speci c installation CONNECTING EXTERNAL CONTROLS If this ERV is equipp...

Page 4: ...und on the Internet at www abb com drives and selecting Sales Support and Service Network Softkey Auto OFF Hand Softkey Help Key Up Down Buttons The function of each Softkey changes and is shown just...

Page 5: ...ected directly to the VFD See Fig 2 3 SPEED SIGNAL CONNECTIONS Any SPEED Signal connections are made directly to the VFD see Figures 4 6 7 The VFDs can accept 4 20mA or 0 10vdc analog control signals...

Page 6: ...9 10 11 12 15 8 7 6 5 4 3 2 1 AGND A01 AGND AI2 10V AGND AI1 SCR VFD FA 9 10 11 12 15 8 7 6 5 4 3 2 1 AGND A01 AGND AI2 10V AGND AI1 SCR VFD EA 17 19 PARAMETER SETTINGS FA VFD Parameter Setting Param...

Page 7: ...Speed Signal to the EA VFD Use shielded cable and ground the shield to Terminal 1 on either VFD 1 1 9 1 6 5 9 XVLQJ YGF 1 1 9 1 6 5 9 XVLQJ P RQQHFWLRQV IRU YGF RQWUROOHU 6HW XPSHU RU VZLWFK WR 27720...

Page 8: ...in this example since it is controlled as a Follower If it is desired that the VFDs should shut off when CO2 levels drop below a setpoint connect the Normally Open contacts of the CO2 controller term...

Page 9: ...auspices of the American Society of Heating Refrigerating and Air Conditioning Engineers ASHRAE BACnet is an American national standard a European standard a national standard in more than 30 countrie...

Page 10: ...ange the VFD parameters as required for the speci c controls system see Control Connections and VFD Parameters below for examples see also the ABB Manuals Press the AUTO switch on the keypad 230V Powe...

Page 11: ...eter 3 Press the SAVE softkey to set the Parameter to the selected value TO VIEW ONLY CHANGED VFD PARAMETERS 1 If EXIT is displayed above the left softkey press softkey repeatedly until MENU appears a...

Page 12: ...or scaling and offsetting the input to the VFD output 1302 MAXIMUM AI1 100 100 Sets maximum value for analog input Used for scaling and offsetting the input to the VFD output 1304 MINIMUM AI2 20 1 20...

Page 13: ...abb com drives SUMMARY TABLE OF COMMONLY USED PARAMETERS CONT NOTE Parameters not listed in this Table are shipped at ABB s default settings for the HVAC Application Macro Name Selection ABB HVAC Defa...

Page 14: ...NSE LEVEL is the level of measurement of indoor air quality or occupancy at which the ERV should be operating at the Design Maximum Supply Air ow Do not change PARAMETER 2003 MAX CURRENT from RenewAir...

Page 15: ...he Maximum Response Level The engineer wants the ERV to Run at a minimum of 700 CFM regardless of CO2 levels in order to control the level of indoor air pollutants generated by the furnishings Start t...

Page 16: ...value of the analog signal from the controller when CO2 600ppm 6 Set the parameters that will scale the response of the VFD to the inputs from the CO2 controller Set Parameter 1301 MINIMUM AI 1 to 55...

Reviews: