   12

Ratings, fuses and typical power cables

1) Typical motor power with no overload capacity (nominal use). The kilowatt ratings apply to most IEC 4-pole motors. The
horsepower ratings apply to most NEMA 4-pole motors.
2) For IEC installations, ABB recommends aR fuses. The gG fuses can be used for frames R3 and R6 if they operate rapidly 

enough (max. 0.1 seconds). The operating time depends on the supply network impedance and the cross-sectional area and 

length of the supply cable. Obey the local regulations. See hardware manual for guidelines in selecting between aR and gG 

fuses, and for additional fuse alternatives

.

3) The recommended branch protection fuses must be used to maintain the IEC/EN/UL 61800-5-1 and CSA C22.2 No. 274 

certifications. Refer to note 6 for circuit breaker protection.
4) IEC 61439-1:

 

The drive is suitable for use on a circuit capable of delivering not more than 65 kA

 

when protected by the 

fuses given in this table. 
5) UL 61800-5-1, CSA C22.2 No. 274: The drive is suitable for use on a circuit capable of delivering not more than 100 kA 

symmetrical amperes (rms) at 480 V maximum when protected by the ABB recommended fuses.
6) Refer to 

Alternate Fuses, MMPs and Circuit Breakers for ABB Drives

 (

3AXD50000645015

 [English]) for additional UL fuses 

and circuit breakers that can be used as branch circuit protection. 
7) Class J, CC, and CF fuses are also allowed at the same nominal current and voltage ratings.
8) These losses are not calculated according to IEC 61800-9-2.
9) IEC Installations: The cable sizing is based on max. 9 cables laid on a cable ladder side by side, three ladder type trays one 

on top of the other, ambient temperature 30 °C, PV insulation, surface temperature 70 °C (EN 60204-1 and IEC 60364-5-52/

2001). For other conditions, size the cables according to local safety regulations, appropriate input voltage and the load 

current of the drive.
10) NEC Installations:

 

The cable sizing is based on NEC Table 310-16 for copper wires, 75 °C (167 °F) wire insulation at 40 °C 

(104 °F) ambient temperature. Not more than three current-carrying conductors in raceway or cable or earth (directly 

buried). For other conditions, size the cables according to local safety regulations, appropriate input voltage and the load 

current of the drive.

ACQ580

-31-… 

IEC 

ratings

Frame 

size

Input 

rating

Output ratings

Motor 

power

1)

Fuses

3)

Typical power 

cable

9)

Typical 

power 

loss 

8)

gG fuse

4)

(DIN 43620)

aR fuse

2)4)

 (DIN 

43620)

Copper

I

1

I

2

I

Ld

P

Ld

ABB type

Bussmann type

mm

2

W

A

A

A

kW

U

n

 = 3-phase 400 V

09A5-4

R3

8

9.4

8.9

4.0

OFAF000H16

170M1561

3x2,5+2,5

226

12A7-4

R3

10

12.6

12.0

5.5

OFAF000H16

170M1561

3x2,5+2,5

329

018A-4

R3

14

17.0

16.2

7.5

OFAF000H25

170M1563

3x2,5+2,5

395

026A-4

R3

20

25

23.8

11

OFAF000H32

170M1563

3x6+6

579

033A-4

R6

27

32

30

15

OFAF000H40

170M1565

3x10+10

625

039A-4

R6

33

38

36

18.5

OFAF000H50

170M1565

3x10+10

751

046A-4

R6

40

45

43

22

OFAF000H63

170M1566

3x16+16

912

062A-4

R6

51

62

59

30

OFAF000H80

170M1567

3x25+16

1088

073A-4*

R6

63

73

69

37

OFAF000H100

170M1568

3x35+16

1502

088A-4*

R6

76

88

84

45

OFAF000H100

170M1568

3x50+25

1904

106A-4

R8

94

106

101

55

-

170M1569

3x70+35

1877

145A-4

R8

128

145

138

75

-

170M3817

3x95+50

2963

169A-4

R8

154

169

161

90

-

170M5808

3x120+70

3168

206A-4

R8

188

206

196

110

-

170M5809

3x150+70

3990

ACQ580

-31-… 

IEC 

ratings

Frame 

size

Input 

rating

Output ratings

Motor 

power

1)

Fuses

3)

Typical power 

cable

9)

Typical 

power loss 

8)

gG fuse

4)

(DIN 43620)

aR fuse

2)4)

 

(DIN 43620)

Copper

I

1

I

2

I

Ld

P

Ld

ABB type

Bussmann 

type

mm

2

W

A

A

A

kW

U

n

 = 3-phase 480 V

09A5-4

R3

7.0

7.6

7.6

4.0

OFAF000H16

170M1561

3x2.5+2.5

219

12A7-4

R3

9.0

12.0

12.0

5.5

OFAF000H16

170M1561

3x2.5+2.5

278

018A-4

R3

12.0

14.0

14.0

7.5

OFAF000H25

170M1563

3x2.5+2.5

321

026A-4

R3

17.0

23.0

23.0

11

OFAF000H32

170M1563

3x6+6

473

033A-4

R6

24

27

27

15

OFAF000H40

170M1565

3x10+10

625

039A-4

R6

29

34

34

18.5

OFAF000H50

170M1565

3x10+10

711

046A-4

R6

34

44

44

22

OFAF000H63

170M1566

3x16+16

807

062A-4

R6

44

52

52

30

OFAF000H80

170M1567

3x25+16

960

073A-4*

R6

54

65

65

37

OFAF000H100

170M1568

3x35+16

1223

088A-4*

R6

66

77

77

45

OFAF000H100

170M1568

3x50+25

1560

106A-4

R8

82

96

96

55

-

170M1569

3x70+35

1678

145A-4

R8

111

124

124

75

-

170M3817

3x95+50

2237

169A-4

R8

134

156

156

90

-

170M5808

3x120+70

2796

206A-4

R8

163

180

180

110

-

170M5809

3x150+70

3356

Summary of Contents for ACQ580-31 Series

Page 1: ...ive when a rotating permanent magnet motor is connected to it A rotating permanent magnet motor energizes the drive including its input and output terminals Make sure that debris from drilling cutting...

Page 2: ...pair cable for analog signals Use double shielded or single shielded cable for the digital relay and I O signals Do not run 24 V and 115 230 V signals in the same cable Protect the drive and input pow...

Page 3: ...creases the insulation resistance If you think that there is moisture dry the motor and do the measurement again Frame Symmetrically grounded TN S systems center grounded wye Corner grounded delta and...

Page 4: ...l area of the PE conductor is less than 10 mm2 Cu or 16 mm2 Al For example you can use the cable shield in addition to the fourth conductor PE PE L1 L2 L3 UDC U1 W1 M 3 T1 U T2 V T3 W V1 PE PE L1 L2 L...

Page 5: ...strated in the applicable figure 3c Slide the cables through the holes in the cable entry and attach the grommets to the holes 4 Connect the power cables For the tightening torques refer to Terminal d...

Page 6: ...ound the motor cable shield at the motor end For minimum radio frequency interference ground the motor cable shield 360 degrees at the cable entry of the motor terminal box 4b 4c 2 9 N m 2 9 N m 2 N m...

Page 7: ...SCR1 terminal 3 Tie all control cables to the provided cable tie mounts Default I O connections Water default Total load capacity of the auxiliary voltage output 24V X2 10 is 6 0 W 250 mA 24 V DC Term...

Page 8: ...cluded in the delivery 12 Install the cover s 1 7 N m R3 R8 R6 1 7 N m 15 lbf in 2 N m 1 5 lbf ft 2 N m 2 N m 2 N m 1 5 lbf ft 1 2 1 2 IP21 UL Type 1 R3 IP55 UL type 12 R3 IP21 UL type 1 R6 R8 IP55 UL...

Page 9: ...cable shield and connect them to the grounding terminals Ground the shield 360 degrees at the grounding clamp If you use discrete conductors connect the insulated ground conductor to the ground termin...

Page 10: ...Home screen press Menu to enter the Main Menu 5 In the Main menu go to Parameters Complete list 95 HW configuration pressing Select repeatedly to select parameter 95 01 6 In parameter 95 01 Supply vol...

Page 11: ...Communication control Refresh settings Validates any changed EFB configuration settings Use this after changing any parameters in group 58 58 14 Communication loss action 58 17 Transmit delay 58 28 EF...

Page 12: ...hree current carrying conductors in raceway or cable or earth directly buried For other conditions size the cables according to local safety regulations appropriate input voltage and the load current...

Page 13: ...14 321 023A 4 R3 17 0 23 0 23 0 15 JJS 35 10 473 027A 4 R6 24 27 27 20 JJS 40 8 625 034A 4 R6 29 34 34 25 JJS 50 8 711 044A 4 R6 34 44 44 30 JJS 60 6 807 052A 4 R6 44 52 52 40 JJS 80 4 960 065A 4 R6...

Page 14: ...ides all other functions of the drive Wiring The safety contacts must open close within 200 ms of each other Double shielded twisted pair cable is recommended for the connection The maximum length of...