6.  Remove the covers.

7.  Make sure that the drive is compatible with the grounding system

You can connect all drives to a symmetrically grounded TN-S system (center-grounded wye). If you install the drive to a 

different system, you may need to remove the EMC screw (disconnect the EMC filter) and/or remove the VAR screw 

(disconnect the varistor circuit).

8.  Measure the insulation resistance of the power cables and the motor

Measure the insulation resistance of the input cable before you connect it to the drive. Obey local regulations.
Measure the insulation resistance of the motor cable and motor when the 

cable is disconnected from the drive. Measure the insulation resistance 

between each phase conductor and the PE conductor. Use a measuring 

voltage of 1000 V DC. The insulation resistance of an ABB motor must be 

more than 100 Mohm (reference value at 25 °C). For the insulation 

resistance of other motors, see the manufacturer’s instructions. Moisture 

inside the motor decreases the insulation resistance. If you think that there 

is moisture, dry the motor and do the measurement again.

Frame

Symmetrically grounded 

TN-S systems (center-

grounded wye)

Corner-grounded delta 

and midpoint-grounded 

delta systems

IT systems (ungrounded 

or high-resistance 

grounded)

TT systems

 1) 2)

1) A residual current device must be installed in the supply system. In NEC installations the residual current device is only 

required at or above 1000 amps.
2) ABB does not guarantee the EMC category or the operation of the ground leakage detector built inside the drive.

R3

Do not remove EMC AC or 

VAR screws.

Do not remove EMC or 

VAR screws.

Remove EMC and VAR 

screws.

Remove EMC and VAR 

screws.

R6

Do not remove EMC AC or 

VAR screws.

Remove EMC DC screw. 
Do not remove EMC AC or 
VAR screws. See Note 1 
below.

Remove EMC AC, EMC DC 

and VAR screws.

Remove EMC AC, EMC DC 

and VAR screws.

R8

Do not remove EMC AC or 

VAR screws.

Remove EMC DC and VAR 

screws.

Remove EMC DC and VAR 

screws.

Remove EMC DC and VAR 

screws.

2

1

IP21 (UL Type 1) – R3

IP21 (UL Type 1) – R6, R8 

IP55 (UL Type 12) – 

R6, R8 

2

1b

1a

IP55 (UL Type 12) – R3

2

1b

1a

3a

3b

4

1000 V DC,

>

 100 Mohm

U1-PE, V1-PE, W1-PE

ohm

M

3~

U1

V1

W1

PE

Summary of Contents for ACQ580-31 Series

Page 1: ...ive when a rotating permanent magnet motor is connected to it A rotating permanent magnet motor energizes the drive including its input and output terminals Make sure that debris from drilling cutting...

Page 2: ...pair cable for analog signals Use double shielded or single shielded cable for the digital relay and I O signals Do not run 24 V and 115 230 V signals in the same cable Protect the drive and input pow...

Page 3: ...creases the insulation resistance If you think that there is moisture dry the motor and do the measurement again Frame Symmetrically grounded TN S systems center grounded wye Corner grounded delta and...

Page 4: ...l area of the PE conductor is less than 10 mm2 Cu or 16 mm2 Al For example you can use the cable shield in addition to the fourth conductor PE PE L1 L2 L3 UDC U1 W1 M 3 T1 U T2 V T3 W V1 PE PE L1 L2 L...

Page 5: ...strated in the applicable figure 3c Slide the cables through the holes in the cable entry and attach the grommets to the holes 4 Connect the power cables For the tightening torques refer to Terminal d...

Page 6: ...ound the motor cable shield at the motor end For minimum radio frequency interference ground the motor cable shield 360 degrees at the cable entry of the motor terminal box 4b 4c 2 9 N m 2 9 N m 2 N m...

Page 7: ...SCR1 terminal 3 Tie all control cables to the provided cable tie mounts Default I O connections Water default Total load capacity of the auxiliary voltage output 24V X2 10 is 6 0 W 250 mA 24 V DC Term...

Page 8: ...cluded in the delivery 12 Install the cover s 1 7 N m R3 R8 R6 1 7 N m 15 lbf in 2 N m 1 5 lbf ft 2 N m 2 N m 2 N m 1 5 lbf ft 1 2 1 2 IP21 UL Type 1 R3 IP55 UL type 12 R3 IP21 UL type 1 R6 R8 IP55 UL...

Page 9: ...cable shield and connect them to the grounding terminals Ground the shield 360 degrees at the grounding clamp If you use discrete conductors connect the insulated ground conductor to the ground termin...

Page 10: ...Home screen press Menu to enter the Main Menu 5 In the Main menu go to Parameters Complete list 95 HW configuration pressing Select repeatedly to select parameter 95 01 6 In parameter 95 01 Supply vol...

Page 11: ...Communication control Refresh settings Validates any changed EFB configuration settings Use this after changing any parameters in group 58 58 14 Communication loss action 58 17 Transmit delay 58 28 EF...

Page 12: ...hree current carrying conductors in raceway or cable or earth directly buried For other conditions size the cables according to local safety regulations appropriate input voltage and the load current...

Page 13: ...14 321 023A 4 R3 17 0 23 0 23 0 15 JJS 35 10 473 027A 4 R6 24 27 27 20 JJS 40 8 625 034A 4 R6 29 34 34 25 JJS 50 8 711 044A 4 R6 34 44 44 30 JJS 60 6 807 052A 4 R6 44 52 52 40 JJS 80 4 960 065A 4 R6...

Page 14: ...ides all other functions of the drive Wiring The safety contacts must open close within 200 ms of each other Double shielded twisted pair cable is recommended for the connection The maximum length of...

Page 15: ...fety function is used for safety component functionality Adjustable speed electrical power drive systems Part 5 2 Safety requirements Functional Safety of machinery Functional safety of safety related...

Reviews: