* These ratings are not to be used for drives with degree of protection of IP55 (UL Type 12) B056.

Terminal data

For tightening torques of grounding terminals, see sectio

Connect the power cables

.

* Maximum cable diameter accepted.

Notes:

• 

The minimum specified wire size does not necessarily have sufficient current carrying capacity at maximum load. Make 

sure the installation complies with local laws and regulations.

• 

For IEC installations using mm

2

 

cable,

 

the terminals do not accept a conductor that is one size larger than the 

recommended wire size. For NEC installations using AWG cable, this applies only to the R8 frame 206A drive.

• 

The maximum number of conductors per terminal is 1.

Dimensions, weights and free space requirements

200 mm (7.9 in) free space is required at top of the drive. 
300 mm (11.8 in) free space (when measured from the drive base without the cable box) is required at bottom of the drive.

Ambient conditions

ACQ580

-31-… 

NEC 

ratings

Frame 

size

Input rating

Output ratings

Motor 

power

1)

Fuses

3)

Typical 

power cable

Typical 

power loss 

8)

UL class T

5)6)7)

Copper

I

1

I

2

I

Ld

P

Ld

Bussmann type

AWG 

10)

W

A

A

A

hp

U

n

 = 3-phase 480 V

07A6-4

R3

7.0

7.6

7.6

5.0

JJS-15

14

219

012A-4

R3

9.0

12.0

12.0

7.5

JJS-20

14

278

014A-4

R3

12.0

14.0

14.0

10

JJS-25

14

321

023A-4

R3

17.0

23.0

23.0

15

JJS-35

10

473

027A-4

R6

24

27

27

20

JJS-40

8

625

034A-4

R6

29

34

34

25

JJS-50

8

711

044A-4

R6

34

44

44

30

JJS-60

6

807

052A-4

R6

44

52

52

40

JJS-80

4

960

065A-4*

R6

54

65

65

50

JJS-90

2

1223

077A-4*

R6

66

77

77

60

JJS-110

2

1560

096A-4

R8

82

96

96

75

JJS-150

1/0

1678

124A-4

R8

111

124

124

100

JJS-200

2/0

2237

156A-4

R8

134

156

156

125

JJS-225

4/0

2796

180A-4

R8

163

180

180

150

JJS-300

250 MCM

3356

Frame size

Cable entries

L1, L2, L3, T1/U, T2/V, T3/W, UDC+ and UDC- terminals

pcs

Max. cable 

diameter

*

Wire size

Tightening torque

mm

in

mm

2

AWG

N·m

lbf·ft

R3

3

23

0.91

0.5…16.0

20…6

1.7

1.3

R6

3

45

1.77

6.0…70.0

10…2/0

5.6

4.1

R8

3

45

1.77

25…150

4…300MCM

30

22.5

Frame 
size

Weight

Height

Width

Depth

kg

lb

mm

in

mm

in

mm

in

IP21, UL Type 1
R3

21.3

46.97

495

19.49

205

8.06

354

13.93

R6

61.0

134.51

771

30.35

252

9.91

393

15.46

R8

118

260.19

965

38.01

300

11.81

438

17.23

IP55, UL Type 12 (B056)
R3

21.3

46.97

490

19.29

205

8.06

360

14.17

R6

63.0

138.92

771

30.35

252

9.92

448

17.65

R8

124

273.42

965

37.99

300

11.81

496

19.53

Installation altitude

0 … 4000 m (0 … 13123 ft) above sea level. The output current must be derated at 

altitudes above 1000 m (3281 ft). The derating is 1% for each 100 m (328 ft) above 

1000 m (3281 ft).

Surrounding air temperature

Operation: -15 … +50 °C (5 … 122 °F). Frost is not permitted. The rated output current 
must be derated by 1% for each 1 °C (1.8 °F) over 40 °C (104 °F). Storage (in the package): 
-40 to +70 °C (-40 to +158 °F).

Summary of Contents for ACQ580-31 Series

Page 1: ...ive when a rotating permanent magnet motor is connected to it A rotating permanent magnet motor energizes the drive including its input and output terminals Make sure that debris from drilling cutting...

Page 2: ...pair cable for analog signals Use double shielded or single shielded cable for the digital relay and I O signals Do not run 24 V and 115 230 V signals in the same cable Protect the drive and input pow...

Page 3: ...creases the insulation resistance If you think that there is moisture dry the motor and do the measurement again Frame Symmetrically grounded TN S systems center grounded wye Corner grounded delta and...

Page 4: ...l area of the PE conductor is less than 10 mm2 Cu or 16 mm2 Al For example you can use the cable shield in addition to the fourth conductor PE PE L1 L2 L3 UDC U1 W1 M 3 T1 U T2 V T3 W V1 PE PE L1 L2 L...

Page 5: ...strated in the applicable figure 3c Slide the cables through the holes in the cable entry and attach the grommets to the holes 4 Connect the power cables For the tightening torques refer to Terminal d...

Page 6: ...ound the motor cable shield at the motor end For minimum radio frequency interference ground the motor cable shield 360 degrees at the cable entry of the motor terminal box 4b 4c 2 9 N m 2 9 N m 2 N m...

Page 7: ...SCR1 terminal 3 Tie all control cables to the provided cable tie mounts Default I O connections Water default Total load capacity of the auxiliary voltage output 24V X2 10 is 6 0 W 250 mA 24 V DC Term...

Page 8: ...cluded in the delivery 12 Install the cover s 1 7 N m R3 R8 R6 1 7 N m 15 lbf in 2 N m 1 5 lbf ft 2 N m 2 N m 2 N m 1 5 lbf ft 1 2 1 2 IP21 UL Type 1 R3 IP55 UL type 12 R3 IP21 UL type 1 R6 R8 IP55 UL...

Page 9: ...cable shield and connect them to the grounding terminals Ground the shield 360 degrees at the grounding clamp If you use discrete conductors connect the insulated ground conductor to the ground termin...

Page 10: ...Home screen press Menu to enter the Main Menu 5 In the Main menu go to Parameters Complete list 95 HW configuration pressing Select repeatedly to select parameter 95 01 6 In parameter 95 01 Supply vol...

Page 11: ...Communication control Refresh settings Validates any changed EFB configuration settings Use this after changing any parameters in group 58 58 14 Communication loss action 58 17 Transmit delay 58 28 EF...

Page 12: ...hree current carrying conductors in raceway or cable or earth directly buried For other conditions size the cables according to local safety regulations appropriate input voltage and the load current...

Page 13: ...14 321 023A 4 R3 17 0 23 0 23 0 15 JJS 35 10 473 027A 4 R6 24 27 27 20 JJS 40 8 625 034A 4 R6 29 34 34 25 JJS 50 8 711 044A 4 R6 34 44 44 30 JJS 60 6 807 052A 4 R6 44 52 52 40 JJS 80 4 960 065A 4 R6...

Page 14: ...ides all other functions of the drive Wiring The safety contacts must open close within 200 ms of each other Double shielded twisted pair cable is recommended for the connection The maximum length of...

Page 15: ...fety function is used for safety component functionality Adjustable speed electrical power drive systems Part 5 2 Safety requirements Functional Safety of machinery Functional safety of safety related...

Reviews: