3.  Select the cables and fuses

• 

Select the power cables. Obey the local regulations.

Input power cable:

 Use symmetrical shielded cable (VFD cable) for the best EMC performance. NEC installations: 

Conduit with continuous conductivity is also allowed and must be grounded on both ends.

Motor cable:

 ABB recommends symmetrically shielded VFD motor cable to reduce bearing current and wear and 

stress on motor insulation and to provide the best EMC performance. Although not recommended, conductors 

inside continuously conductive conduit is allowed in NEC installations. Ground conduit on both ends.

Power cable types:

 IEC installations: Use copper cables. Aluminum cables can only be used with frame sizes R6 and 

R8, except the biggest R8. NEC installations: Only copper conductors are allowed.

Current rating:

 max. load current.

Voltage rating (minimum):

 IEC installations: 600 V AC cable is accepted for up to 500 V AC. NEC installations: 1000 V 

AC for 480 V AC motors. 600 V AC for 480 V AC power line.

Temperature rating:

 IEC installations: Select a cable rated for at least 70

 

°C maximum permissible temperature of 

conductor in continuous use. NEC installations: Use 75 °C conductors minimum. Insulation temperature can be 

higher as long as the ampacity is based on 75 °C conductors. 

• 

Select the control cables. 

Use double-shielded twisted-pair cable for analog signals. Use double-shielded or single-shielded cable for the 

digital, relay and I/O signals. Do not run 24 V and 115/230 V signals in the same cable.

• 

Protect the drive and input power cable with the correct fuses. See 

Ratings, fuses and typical power cables

.

4.  Examine the installation site

Examine the drive installation site. Make sure that:

• 

The installation site is sufficiently ventilated or cooled to remove heat from the drive.

• 

The ambient conditions of the drive meet the specifications. See 

Ambient conditions

.

• 

The wall behind the drive and the material above and below the unit is of non-flammable material.

• 

The installation surface is as close to vertical as possible and strong enough to support the drive.

• 

There is sufficient free space around the drive for cooling, maintenance and operation. For the minimum free space 

requirements, refer to 

Dimensions, weights and free space requirements

.

• 

There are no sources of strong magnetic fields such as high-current single-core conductors or contactor coils near the 

drive. A strong magnetic field can cause interference or inaccuracy in the operation of the drive.

5.  Install the drive on the wall

Select fasteners that comply with local requirements applicable to wall surface materials, drive weight and application. For 

drive weights, refer to 

Dimensions, weights and free space requirements

R3

R6

R8

mm

in

mm

in

mm

in

a

474

18.66

753

29.64

945

37.20

b

160

6.29

213

8.38

263

10.35

a

b

30

0

200 

[7.87]

[1

1.

81

]

1

2

3

4

R3: M5 (#10)

R6: M8 (5/16”)

R8: M8 (5/16”)

Summary of Contents for ACQ580-31 Series

Page 1: ...ive when a rotating permanent magnet motor is connected to it A rotating permanent magnet motor energizes the drive including its input and output terminals Make sure that debris from drilling cutting...

Page 2: ...pair cable for analog signals Use double shielded or single shielded cable for the digital relay and I O signals Do not run 24 V and 115 230 V signals in the same cable Protect the drive and input pow...

Page 3: ...creases the insulation resistance If you think that there is moisture dry the motor and do the measurement again Frame Symmetrically grounded TN S systems center grounded wye Corner grounded delta and...

Page 4: ...l area of the PE conductor is less than 10 mm2 Cu or 16 mm2 Al For example you can use the cable shield in addition to the fourth conductor PE PE L1 L2 L3 UDC U1 W1 M 3 T1 U T2 V T3 W V1 PE PE L1 L2 L...

Page 5: ...strated in the applicable figure 3c Slide the cables through the holes in the cable entry and attach the grommets to the holes 4 Connect the power cables For the tightening torques refer to Terminal d...

Page 6: ...ound the motor cable shield at the motor end For minimum radio frequency interference ground the motor cable shield 360 degrees at the cable entry of the motor terminal box 4b 4c 2 9 N m 2 9 N m 2 N m...

Page 7: ...SCR1 terminal 3 Tie all control cables to the provided cable tie mounts Default I O connections Water default Total load capacity of the auxiliary voltage output 24V X2 10 is 6 0 W 250 mA 24 V DC Term...

Page 8: ...cluded in the delivery 12 Install the cover s 1 7 N m R3 R8 R6 1 7 N m 15 lbf in 2 N m 1 5 lbf ft 2 N m 2 N m 2 N m 1 5 lbf ft 1 2 1 2 IP21 UL Type 1 R3 IP55 UL type 12 R3 IP21 UL type 1 R6 R8 IP55 UL...

Page 9: ...cable shield and connect them to the grounding terminals Ground the shield 360 degrees at the grounding clamp If you use discrete conductors connect the insulated ground conductor to the ground termin...

Page 10: ...Home screen press Menu to enter the Main Menu 5 In the Main menu go to Parameters Complete list 95 HW configuration pressing Select repeatedly to select parameter 95 01 6 In parameter 95 01 Supply vol...

Page 11: ...Communication control Refresh settings Validates any changed EFB configuration settings Use this after changing any parameters in group 58 58 14 Communication loss action 58 17 Transmit delay 58 28 EF...

Page 12: ...hree current carrying conductors in raceway or cable or earth directly buried For other conditions size the cables according to local safety regulations appropriate input voltage and the load current...

Page 13: ...14 321 023A 4 R3 17 0 23 0 23 0 15 JJS 35 10 473 027A 4 R6 24 27 27 20 JJS 40 8 625 034A 4 R6 29 34 34 25 JJS 50 8 711 044A 4 R6 34 44 44 30 JJS 60 6 807 052A 4 R6 44 52 52 40 JJS 80 4 960 065A 4 R6...

Page 14: ...ides all other functions of the drive Wiring The safety contacts must open close within 200 ms of each other Double shielded twisted pair cable is recommended for the connection The maximum length of...

Page 15: ...fety function is used for safety component functionality Adjustable speed electrical power drive systems Part 5 2 Safety requirements Functional Safety of machinery Functional safety of safety related...

Reviews: