background image

   5

Connection procedure with VFD cable

For connection procedure with conduits, see 

Connection procedure with conduit

1.

Attach a residual voltage warning sticker in the local language.

2. Frames R6 and R8: Remove the shroud on the power cable terminals. 

Frame R8:

 

For easier installation, you can remove the side plates

.

3. Prepare the power cables:

Remove the rubber grommets of the cables to be installed from the cable entry plate. Remove the unused grommets 

and reinstall with the cone pointing down (3a).

Cut a sufficient hole in the rubber grommet. Slide the grommet onto the cable (3b) with the remaining cone pointing 

down.

Prepare the ends of the input power cable and motor cable as illustrated in the applicable figure (3c). 

Slide the cables through the holes in the cable entry and attach the grommets to the holes. 

4. Connect the power cables. For the tightening torques, refer to 

Terminal data

.

 

Ground the shield 360 degrees by tightening the clamp of the power cable grounding shelf onto the stripped part of 

the cable (4a).

Connect the twisted shield of the cable shields to the grounding terminals (4b).

Frame R8: to install the common mode filter, see 

Related documents

.

Connect the phase conductors of the motor cable to the T1/U, T2/V and T3/W terminals. Connect the phase 

conductors of the input power cable to the L1, L2 and L3 terminals (4c).

Tighten the screws to the torque given in the installation drawing below.

R6

R8

R8

R8

R6

3b

3c

PE

PE

3a

L1 L2 L3

UDC+ UDC

-

T1

/U

T2/

V

T3

/W

4b

4c

1.7 N·m 

4a

1.7 N·m

1.7 N·m

1.7 N·m

L1, L2, L3, T1/U, T2/V, T3/W: 1.7 N·m (15 lbf·in)

R3

(15 lbf·in)

Summary of Contents for ACQ580-31 Series

Page 1: ...ive when a rotating permanent magnet motor is connected to it A rotating permanent magnet motor energizes the drive including its input and output terminals Make sure that debris from drilling cutting...

Page 2: ...pair cable for analog signals Use double shielded or single shielded cable for the digital relay and I O signals Do not run 24 V and 115 230 V signals in the same cable Protect the drive and input pow...

Page 3: ...creases the insulation resistance If you think that there is moisture dry the motor and do the measurement again Frame Symmetrically grounded TN S systems center grounded wye Corner grounded delta and...

Page 4: ...l area of the PE conductor is less than 10 mm2 Cu or 16 mm2 Al For example you can use the cable shield in addition to the fourth conductor PE PE L1 L2 L3 UDC U1 W1 M 3 T1 U T2 V T3 W V1 PE PE L1 L2 L...

Page 5: ...strated in the applicable figure 3c Slide the cables through the holes in the cable entry and attach the grommets to the holes 4 Connect the power cables For the tightening torques refer to Terminal d...

Page 6: ...ound the motor cable shield at the motor end For minimum radio frequency interference ground the motor cable shield 360 degrees at the cable entry of the motor terminal box 4b 4c 2 9 N m 2 9 N m 2 N m...

Page 7: ...SCR1 terminal 3 Tie all control cables to the provided cable tie mounts Default I O connections Water default Total load capacity of the auxiliary voltage output 24V X2 10 is 6 0 W 250 mA 24 V DC Term...

Page 8: ...cluded in the delivery 12 Install the cover s 1 7 N m R3 R8 R6 1 7 N m 15 lbf in 2 N m 1 5 lbf ft 2 N m 2 N m 2 N m 1 5 lbf ft 1 2 1 2 IP21 UL Type 1 R3 IP55 UL type 12 R3 IP21 UL type 1 R6 R8 IP55 UL...

Page 9: ...cable shield and connect them to the grounding terminals Ground the shield 360 degrees at the grounding clamp If you use discrete conductors connect the insulated ground conductor to the ground termin...

Page 10: ...Home screen press Menu to enter the Main Menu 5 In the Main menu go to Parameters Complete list 95 HW configuration pressing Select repeatedly to select parameter 95 01 6 In parameter 95 01 Supply vol...

Page 11: ...Communication control Refresh settings Validates any changed EFB configuration settings Use this after changing any parameters in group 58 58 14 Communication loss action 58 17 Transmit delay 58 28 EF...

Page 12: ...hree current carrying conductors in raceway or cable or earth directly buried For other conditions size the cables according to local safety regulations appropriate input voltage and the load current...

Page 13: ...14 321 023A 4 R3 17 0 23 0 23 0 15 JJS 35 10 473 027A 4 R6 24 27 27 20 JJS 40 8 625 034A 4 R6 29 34 34 25 JJS 50 8 711 044A 4 R6 34 44 44 30 JJS 60 6 807 052A 4 R6 44 52 52 40 JJS 80 4 960 065A 4 R6...

Page 14: ...ides all other functions of the drive Wiring The safety contacts must open close within 200 ms of each other Double shielded twisted pair cable is recommended for the connection The maximum length of...

Page 15: ...fety function is used for safety component functionality Adjustable speed electrical power drive systems Part 5 2 Safety requirements Functional Safety of machinery Functional safety of safety related...

Reviews: