background image

   11

Motor overload protection

The motor thermal overload protection can use motor temperature devices or can be estimated using a motor model 

defined by parameters. The motor thermal overload protection is set to motor current and motor class curves as default. To 

enable protection using motor model parameters or measurement devices, set parameter 

35.11

 and subsequent 

parameters through 

35.55. 

To adjust motor class curves (default is class 20), change parameters 

35.56

 and 

35.57

Use the information key ( ) on the drive control panel for more information on setting group 35 parameters. You must set 

the drive overload parameters correctly, or motor damage could occur. 

Fieldbus communication

To configure the embedded fieldbus communication for Modbus RTU, you must set at least these parameters:

Other parameters related to the fieldbus configuration:

Warnings and faults

Parameter

Setting

Description

20.01 Ext1 commands

Embedded 

fieldbus

Selects fieldbus as the source for the start and stop commands when 

EXT1 is selected as the active control location.

22.11 Speed ref1 source

EFB ref1

Selects a reference received through the embedded fieldbus interface 

as speed reference 1.

28.11 Frequency ref1 source

EFB ref1

Selects a reference received through the embedded fieldbus interface 

as frequency reference 1.

58.01 Protocol enable

Modbus RTU

Initializes embedded fieldbus communication.

58.03 Node address

1 (default)

Node address. There must be no two nodes with the same node 

address on-line.

58.04 Baud rate

19.2 kbps (default) Defines the communication speed of the link. Use the same setting as 

in the master station.

58.05 Parity

8 EVEN 1 (default) Selects the parity and stop bit setting. Use the same setting as in the 

master station.

58.06 Communication control

Refresh settings

Validates any changed EFB configuration settings. Use this after 

changing any parameters in group 58.

58.14 Communication loss 

action

58.17 Transmit delay

58.28 EFB act1 type

58.34 Word order

58.15 Communication loss 

mode

58.25 Control profile

58.31 EFB act1 transparent 

source

58.101 Data I/O 1 

58.114 Data I/O 14

58.16 Communication loss 

time

58.26 EFB ref1 type

58.33 Addressing mode

Warning

Fault Aux. code

Description

-

2281

Current calibration

Fault: Output phase current measurement fault.

A2B1

2310

Overcurrent

The output current is more than the internal limit. This can also be caused by 

an earth fault or phase loss.

A2B3

2330

Earth leakage

A load unbalance that is typically caused by an earth fault in the motor or the 

motor cable.

A2B4

2340

Short circuit

There is a short-circuit in the motor or the motor cable.

3E00

3130

Input phase loss

The intermediate DC circuit voltage oscillates due to missing input power 

line phase.

-

3181

Wiring or earth fault

Incorrect input and motor cable connection.

A3A1

3210

DC link overvoltage

Intermediate DC circuit voltage is too high.

A3A2

3220

DC link undervoltage

Intermediate DC circuit voltage is too low.

-

3381

Output phase loss

All three phases are not connected to the motor.

-

5090

STO hardware failure

STO hardware diagnostics has detected hardware failure. Contact ABB.

A5A0

5091

Safe torque off

The Safe torque off (STO) function is active.

A7CE

6681

EFB comm loss

Break in embedded fieldbus communication.

A7C1

7510

FBA A communication

Communication lost between drive (or PLC) and fieldbus adapter.

A7AB

-

Extension I/O 

configuration failure

The I/O extension module types and locations specified by parameters do 

not match the detected configuration.

AFF6

-

Identification run

The motor ID run occurs at the next start.

-

FA81

Safe torque off 1 loss

The Safe torque off circuit 1 is broken.

-

FA82

Safe torque off 2 loss

The Safe torque off circuit 2 is broken.

?

Summary of Contents for ACQ580-31 Series

Page 1: ...ive when a rotating permanent magnet motor is connected to it A rotating permanent magnet motor energizes the drive including its input and output terminals Make sure that debris from drilling cutting...

Page 2: ...pair cable for analog signals Use double shielded or single shielded cable for the digital relay and I O signals Do not run 24 V and 115 230 V signals in the same cable Protect the drive and input pow...

Page 3: ...creases the insulation resistance If you think that there is moisture dry the motor and do the measurement again Frame Symmetrically grounded TN S systems center grounded wye Corner grounded delta and...

Page 4: ...l area of the PE conductor is less than 10 mm2 Cu or 16 mm2 Al For example you can use the cable shield in addition to the fourth conductor PE PE L1 L2 L3 UDC U1 W1 M 3 T1 U T2 V T3 W V1 PE PE L1 L2 L...

Page 5: ...strated in the applicable figure 3c Slide the cables through the holes in the cable entry and attach the grommets to the holes 4 Connect the power cables For the tightening torques refer to Terminal d...

Page 6: ...ound the motor cable shield at the motor end For minimum radio frequency interference ground the motor cable shield 360 degrees at the cable entry of the motor terminal box 4b 4c 2 9 N m 2 9 N m 2 N m...

Page 7: ...SCR1 terminal 3 Tie all control cables to the provided cable tie mounts Default I O connections Water default Total load capacity of the auxiliary voltage output 24V X2 10 is 6 0 W 250 mA 24 V DC Term...

Page 8: ...cluded in the delivery 12 Install the cover s 1 7 N m R3 R8 R6 1 7 N m 15 lbf in 2 N m 1 5 lbf ft 2 N m 2 N m 2 N m 1 5 lbf ft 1 2 1 2 IP21 UL Type 1 R3 IP55 UL type 12 R3 IP21 UL type 1 R6 R8 IP55 UL...

Page 9: ...cable shield and connect them to the grounding terminals Ground the shield 360 degrees at the grounding clamp If you use discrete conductors connect the insulated ground conductor to the ground termin...

Page 10: ...Home screen press Menu to enter the Main Menu 5 In the Main menu go to Parameters Complete list 95 HW configuration pressing Select repeatedly to select parameter 95 01 6 In parameter 95 01 Supply vol...

Page 11: ...Communication control Refresh settings Validates any changed EFB configuration settings Use this after changing any parameters in group 58 58 14 Communication loss action 58 17 Transmit delay 58 28 EF...

Page 12: ...hree current carrying conductors in raceway or cable or earth directly buried For other conditions size the cables according to local safety regulations appropriate input voltage and the load current...

Page 13: ...14 321 023A 4 R3 17 0 23 0 23 0 15 JJS 35 10 473 027A 4 R6 24 27 27 20 JJS 40 8 625 034A 4 R6 29 34 34 25 JJS 50 8 711 044A 4 R6 34 44 44 30 JJS 60 6 807 052A 4 R6 44 52 52 40 JJS 80 4 960 065A 4 R6...

Page 14: ...ides all other functions of the drive Wiring The safety contacts must open close within 200 ms of each other Double shielded twisted pair cable is recommended for the connection The maximum length of...

Page 15: ...fety function is used for safety component functionality Adjustable speed electrical power drive systems Part 5 2 Safety requirements Functional Safety of machinery Functional safety of safety related...

Reviews: