ACH550 Installation, Operation and Maintenance Manual
71
ACH550 E-Clipse Bypass
Fault History
See page
28
.
3102
PMAP FILE
Parameter file is
corrupt
Cycle Power
Contact ABB with
information that
preceeded fault
3201
T1 OVERLOAD
T1 program cycle is
overloaded
NA
Contact ABB with
information that
proceeded fault
Cycle Power
Replace RBCU
3202
T2 OVERLOAD
T2 program cycle is
overloaded
NA
Contact ABB with
information that
proceeded fault
Cycle Power
Replace RBCU
3203
T3 OVERLOAD
T3 program cycle is
overloaded
NA
Contact ABB with
information that
proceeded fault
Cycle Power
Replace RBCU
3204
STACK
OVERFLOW
Program cycle is
overloaded
NA
Contact ABB with
information that
proceeded fault
Cycle Power
Replace RBCU
3205
UNKNOWN CB
Bypass control board
type is unknown.
Firmware is not
compatible with control
board in RBCU.
Firmware 93F and
greater compatible with
all RCBU hardware.
Firmware 93D and
earlier can only be
loaded in RBCU Rev D
and earlier.
3206
UNKNOWN DRIVE
Drive reports rating not
found in bypass
software
Drive does not match
drives configured in
bypass RBCU
Replace RBCU or
reload with most
current firmware
3207
UNKNOWN
BYPASS
NA
NA
Replace RBCU or load
most current firmware
Contact ABB at
1-800-HELP-365
option 4
Replace RBCU or load
most current firmware
Fault
Code
Fault Name In
Panel
Fault
Possible Cause
Corrective Action