![ABB ACH550-UH HVAC Installation, Operation & Maintenance Manual Download Page 37](http://html1.mh-extra.com/html/abb/ach550-uh-hvac/ach550-uh-hvac_installation-operation-and-maintenance-manual_3361774037.webp)
ACH550 Installation, Operation and Maintenance Manual
37
ACH550-UH
Frame Sizes R7/R8 – UL type 12 enclosure exhaust filters
The exhaust filters in the R7/R8 UL type 12 enclosure are located in the exhaust box
at the top of the enclosure.
There are 2 filter frames attached to the exhaust
box.
1. Remove each filter frame:
• Lift up on the filter frame until it slides
approximately 3/4 inch.
• Pull away from the exhaust box to remove.
2. For each filter frame, remove the
wire retainers that hold the filters
in place:
• Lay the filter frames on a flat
work surface.
• The wire retainers have a
square “U” shape. Remove by
squeezing the open end of the
“U” towards the middle of the
“square” until the retainer top (open end of “U”) clears the filter frame.
• Save the retainers for reinstallation.
3. Remove and inspect the filter.
4. Install clean filters.
Note:
When installing DUSTLOK® filter media, the white side
must face to outside of the cabinet, and the orange side
faces in.
Be sure to tuck the filter edges into the groove around the
entire filter frame. This detail is very important for proper
operation.
5. Reinstall the filter restrainers.
• Insert the base of a retainer
(bottom of “U” shape) into a
filter frame channel.
• Squeeze the open end of the
“U” until it clears the filter
frame.
• Seat the open end of the “U”
in the filter frame channel.
• Release the retainer to its relaxed, square shape.
PC00021
PC00001
PC00019
PC00022
PC00001
PC00019