Installing the PROFIBUS DP Interface, CI854/CI854A/TP854
Section 2 Installation
118
3BSE036351-510 A
Installation of PROFIBUS DP
For installation of the fieldbus and recommended certified fieldbus devices and
components, see fieldbus documentation and
Appendix C, Recommended
Components
. The PROFIBUS DP must be connected with shielded twisted pair
cables.
Table 15. CI854/CI854A – PROFIBUS DP Connector
PIN
Designation
Description
1
Shield
Shield/protective ground
2
–
Not Used
3
RxD/TxD-P
Receive/Transmit Data P-line (B-line)
4
CNTR-P
Indicates Direction to Repeater (TTL)
5
DGND
Digital Ground
6
VP
+5 V, for terminating resistors
7
–
–
8
RxD/TxD-N
Receive/Transmit Data
N-line (A-line)
9
DGND
Digital Ground
Note that there is no unit redundancy for the CI854 unit. Only for CI854A.
Hot swap is supported for CI854A (not CI854).
Summary of Contents for AC 800M
Page 1: ...Power and productivity for a better worldTM AC 800M Controller Hardware System Version 5 1...
Page 2: ......
Page 3: ...AC 800M Controller Hardware System Version 5 1...
Page 150: ...Mounting Dimensions for Proper Ventilation Section 2 Installation 150 3BSE036351 510 A...