Section 2 Installation
Installing the FOUNDATION Fieldbus High Speed Ethernet Interface,
3BSE036351-510 A
123
Installing the FOUNDATION Fieldbus High Speed Ethernet
Interface, CI860/TP860
The CI860 is powered from the processor unit via the CEX-Bus and requires
therefore no additional external power source.
Use the following procedure to install the CI860/TP860:
1.
Mount the unit onto the DIN-rail, see
Mounting AC 800M Units onto DIN-Rail
on page 65 and
Installing the PM86x/TP830 Processor Unit in Single
Configuration
on page 78.
2.
Connect the Ethernet twisted pair cable to the COM connector on the
baseplate.
3.
Connect the other end of the Ethernet cable to Ethernet network via standard
Ethernet components.
4.
Please make sure to meet the FOUNDATION Fieldbus High Speed Ethernet
specification of the network and the network devices.
Ethernet Twisted Pair Connection
The Ethernet twisted pair is connected via the RJ45 connector located on TP860.
For a description of the connector see
Table 5
on page 84.