18
3BSE036351-510 A
Safety Summary
Electrostatic Sensitive Device
Devices labeled with this symbol require special handling precautions as
described in the installation section.
GENERAL
WARNINGS
Equipment Environment
All components, whether in transportation, operation or storage, must be
in a noncorrosive environment.
Electrical Shock Hazard During Maintenance
Disconnect power or take precautions to insure that contact with ener-
gized parts is avoided when servicing.
SPECIFIC
WARNINGS
Page 67: The AC 800M Controller and associated units must be unpow-
ered and disconnected when being mounted onto a DIN-rail!
Page 68: It is not allowed to manipulate CEX bus baseplates in a powered
and running system. Before changing or removing a baseplate, all CEX
modules on that segment must be removed.
Page 72: AC 800M units must be disconnected from the power source
before removing them from a DIN-rail!
Page 72: It is not allowed to manipulate CEX bus baseplates in a powered
and running system. Before changing or removing a baseplate, all CEX
modules on that segment must be removed.
Page 78: For PM861/PM864/PM865/PM866 insert the RCU Link Termi-
nation plug TB852, at the RCU Link connector. The termination plug must
always be used for PM861/PM864/PM865/PM866 when running in single
configuration. When a redundant processor is running in a single configu-
ration use the RCU Link Cable TK851, if the RCU Link Termination plug
TB852 is not available.
Summary of Contents for AC 800M
Page 1: ...Power and productivity for a better worldTM AC 800M Controller Hardware System Version 5 1...
Page 2: ......
Page 3: ...AC 800M Controller Hardware System Version 5 1...
Page 150: ...Mounting Dimensions for Proper Ventilation Section 2 Installation 150 3BSE036351 510 A...
Page 190: ...Verification of Redundant CPU Section 4 Operation 190 3BSE036351 510 A...