Communication Possibilities
Section 3 Configuration
156
3BSE036351-510 A
Table 19. Interfaces Available on the CEX-Bus
Interface
Number of Interfaces on
CEX-Bus
Number of
ports per
Interface
Maximum of
each
interface
Maximum
total on
CEX-Bus
(1)(2)
(1) PM851/PM851A is restricted to a maximum of one CEX module.
CI851 (PROFIBUS DP)
12
12
1
CI852 (FOUNDATION Fieldbus H1)
12
1
CI853 (RS-232C)
12
2
CI854/CI854A
(PROFIBUS DP)
12
2
CI855
(Ethernet for MasterBus 300)
12
2
CI856 (S100)
12
1
CI857 (INSUM)
6
1
CI858 (DriveBus)
2
3
CI860 (FOUNDATION Fieldbus HSE)
12
1
CI862 (TRIO)
4
1
CI865 (Satt I/O)
4
1
CI867 (Modbus TCP)
12
2
CI868 (IEC 61850)
4
1
(3)
CI869 (AF100)
12
2
CI871 (PROFINET IO)
12
2
(3)
CI872 (MOD5)
4
8
3
CI873 (EtherNet/IP)
4
12
2
(3)
Summary of Contents for AC 800M
Page 1: ...Power and productivity for a better worldTM AC 800M Controller Hardware System Version 5 1...
Page 2: ......
Page 3: ...AC 800M Controller Hardware System Version 5 1...
Page 150: ...Mounting Dimensions for Proper Ventilation Section 2 Installation 150 3BSE036351 510 A...