Installing the PM86x/TP830 Processor Unit in Single Configuration
Section 2 Installation
78
3BSE036351-510 A
Installing the PM86x/TP830 Processor Unit in Single
Configuration
Use the procedure below to install the processor unit along the DIN-rail:
1.
If already mounted, remove the CEX-Bus and ModuleBus terminations from
the sides of the processor unit.
2.
Mount the processor unit, the communication interfaces, and the S800 I/O
units.
The communication interfaces for all PM8xx is on the CEX-Bus to the left of
the processor unit. The S800 I/O units for PM8xx is on the electrical
ModuleBus to the right of the processor unit.
3.
Press them gently together and make sure that the ModuleBus and the CEX-
Bus are correctly connected, via baseplate connectors.
4.
Reinsert the bus terminations into the communication units at farthest away
from the processor unit.
a.
For CEX-Bus TB850 (TB851 if cable TK850 is used), see
Figure 25
on
page 80 and
Figure 26
on page 81. When using BC810, see
Figure 27
on
page 82. If no units are used on the CEX-Bus, no bus termination is
required.
b.
For ModuleBus TB807, refer to the S800 I/O documentation. If no units
are used on the ModuleBus, no bus termination is required.
This topic does not apply to the PM891 processor unit. See
Installing PM891 in
Single Configuration
on page 87.
For PM861/PM864/PM865/PM866 insert the RCU Link Termination plug
TB852, at the RCU Link connector. The termination plug must always be used
for PM861/PM864/PM865/PM866 when running in single configuration.
When a redundant processor is running in a single configuration use the RCU
Link Cable TK851, if the RCU Link Termination plug TB852 is not available.
Summary of Contents for AC 800M
Page 1: ...Power and productivity for a better worldTM AC 800M Controller Hardware System Version 5 1...
Page 2: ......
Page 3: ...AC 800M Controller Hardware System Version 5 1...
Page 150: ...Mounting Dimensions for Proper Ventilation Section 2 Installation 150 3BSE036351 510 A...
Page 190: ...Verification of Redundant CPU Section 4 Operation 190 3BSE036351 510 A...