Make sure that the port/ports used for fast startup is selected in the IO
configuration.
•
Check with the device vendor for optimal settings when using the I/O device
with fast startup. Sometimes device behavior is configurable with a vendor
specific tool or through the network configuration tool. According to the
GSDML file.
•
Check that the switch settings are correct according to below:
-
100 Mbit speed rate with full duplex.
-
Auto negotiation shall be switched off.
-
Disable "switch intelligent features" such as flow control and MDIX
(medium dependent interface crossover) that might cause delays during
startup.
Configuration of AC500 with an IRC5 device in Automation Builder (Control Builder Plus)
Use this procedure to configure the AC500 with an IRC5 device in the Automation
Builder:
Note
Action
In the AC500 project, select the appropri-
ate PROFINET controller.
1
xx1500003223
Double-click on the IRC5 device icon to
select the IRC5 device.
2
In the
PNIO parameters
tab, edit the field
RT Class
to
RT Class 2 Data-RTC-PDU
.
3
ID mismatch on PROFINET controller
If the diagnostics from the PROFINET controller say something like "Peer Port ID
mismatch" or "Peer Chassis ID mismatch":
This can be caused by more than one network connected to the robot controller
using LLDP. For more information, see
Link Layer Discovery Protocol (LLDP) on
70
Application manual - PROFINET Controller/Device
3HAC050969-001 Revision: G
© Copyright 2015-2018 ABB. All rights reserved.
7 Troubleshooting
7.1 Scenarios
Continued
Summary of Contents for 888-2
Page 1: ...ROBOTICS Application manual PROFINET Controller Device ...
Page 28: ...This page is intentionally left blank ...
Page 34: ...This page is intentionally left blank ...
Page 40: ...This page is intentionally left blank ...
Page 48: ...This page is intentionally left blank ...
Page 74: ...This page is intentionally left blank ...
Page 78: ...This page is intentionally left blank ...
Page 86: ......
Page 87: ......