Please see the IET600 user manual for additional information about
vertical and horizontal station communication engineering.
7.5
Importing SCL files to PCM600
The IED engineering tool must be able to receive a SCD file or an ICD file as
import to receive the engineered communication extensions, for example for the
different IEDs.
7.5.1
Importing SCD files
Procedure to import a SCD file to PCM600:
1. Select the station in the plant structure.
2. Right-click the station and select
Import ...
3. Select the file to be imported from the open standard Windows menu and start
the reading.
4. A
SCL Import Options
window opens, which queries how the file should be
IEC09000631-1-en.vsd
IEC09000631 V1 EN
Figure 68:
IEC 61850: Import SCD file
4.1. Click
Ignore Substation Section
to not import the "SSD-file" part of the
SCD-file.
4.2. Click
Don't import IEDs of unknown type
to protect the existing IEDs in
case the SCD file does not match the original configuration in PCM600.
4.3. Click
Replace unknown ...
can be used when it is known, that the file
includes additional IEDs that are needed. The IED of type “Generic IEC
1MRK 511 261-UEN -
Section 7
IEC 61850 communication engineering
650 series
95