Parameter names are shown in italics.
The function can be enabled and disabled with the
Operation
setting.
•
The ^ character in front of an input or output signal name in the function block
symbol given for a function, indicates that the user can set an own signal name
in PCM600.
•
The * character after an input or output signal name in the function block
symbol given for a function, indicates that the signal must be connected to
another function block in the application configuration to achieve a valid
application configuration.
1.4.3
Functions included in 650 series IEDs
Table 1:
Main protection functions
IEC 61850 / Function block
name
ANSI
Function description
T2WPDIF
87T
Transformer differential protection, two winding
T3WPDIF
87T
Transformer differential protection, three winding
REFPDIF
87N
Restricted earth fault protection, low impedance
HZPDIF
87
1Ph High impedance differential protection
GENPDIF
87G
Generator differential protection
ZQMPDIS
21
Five-zone distance protection, Quadrilateral and Mho characteristic
FDPSPDIS
21
Phase selection with load enchroachment, quadrilateral characteristic
FMPSPDIS
21
Faulty phase identification with load enchroachment for mho
ZDARDIR
21
Additional distance protection directional function for earth faults
ZDNRDIR
21
Directional impedance quadrilateral and mho
PPLPHIZ
Phase preference logic
ZMRPSB
68
Power swing detection
ZCVPSOF
Automatic switch onto fault logic, voltage-and current-based
ZGCPDIS
21G
Underimpedance protection for generators and transformers
LEXPDIS
40
Loss of excitation
OOSPPAM
78
Out-of-step protection
LEPDIS
Load enchroachment
Table 2:
Backup protection functions
IEC 61850 / Function
block name
ANSI
Function description
Current protection
PHPIOC
50
Instantaneous phase overcurrent protection
SPTPIOC
50
Instantaneous phase overcurrent protection
OC4PTOC
51/67
Four-step phase overcurrent protection
Table continues on next page
1MRK 511 261-UEN -
Section 1
Introduction
650 series
9
Engineering Manual