IEC08000416.vsd
IEC08000416 V1 EN
Figure 66:
IEC 61850: Export IED file type selection
3. The
SCL Export Options
window opens.
4. Select
Export Private Sections
,
Export As SCL Template
or
Include Goose
Sending IEDs
and click
Export
, see
SCL
Export Options
window according to
file is exported.
IEC08000418.vsd
IEC08000418 V1 EN
Figure 67:
IEC 61850: Export IED file Options
7.4
Engineering of vertical and horizontal
communication in IET600
For IEC 61850 engineering a separate system configuration tool is needed to be
used with PCM600. In PCM600 Ver. 2.3 or earlier the recommended tool is
CCT600. In PCM600 Ver. 2.4 or later the recommended tool is IET600, which is
also included in the PCM600 Engineering Pro installation package.
Procedure for signal engineering for the station by using IET600:
1. Create a project in IET600.
2. Import the SCD file exported from PCM600.
All data sets, report control blocks and GOOSE control blocks
must be located at LD0/LLN0. Due to IED capability, there are
limitations regarding the maximum number of data sets,
1MRK 511 261-UEN -
Section 7
IEC 61850 communication engineering
650 series
93
Engineering Manual