41/54
TLE Scalable Series 40 to 150 UL S1
UPS Installation Guide / REV-B
Fig. 4.9.2-2 Bus connection on first and last units
Note!
Final units, first and
last, of an RPA Parallel
System.
On the two boards P13/P14
– IM0
2
22 – Bus Interface Board,
of the first and last units of an
RPA Parallel System, the switches
SW1-1/2/3/4/5/6
must be in
position ON
(see Fig. 4.9.2-2).
Fig. 4.9.2-3 Bus connection on intermediate units
Note!
Intermediate units of
an RPA Parallel
System.
On the two boards P13/P14 –
IM0
2
22 – Bus Interface Board, of
the intermediate units of an RPA
Parallel System, the switches SW1-
1/2/3/4/5/6
must be in position
OFF
(see Fig.4.9.2-3).