TLE Scalable Series 40 to 150 UL S1
UPS Installation Guide / REV-B
4.4
Place of installation
4.4.1
UPS location
Note!
UPS installation and connection must be performed only by an ABB Service Technician!
If optional cabinets and accessories are included with the UPS, please refer to those accompanying
manuals for installation and operating instructions.
The UPS is intended for use in electrical rooms.
Do not locate or stock easily flammable materials in the same room as the UPS.
It is important to have a clean, dust-free environment provided with proper ventilation and air-conditioning to
keep the ambient temperature within the specified operating range.
The recommended air inlet temperature is from
68°F
(20°C)
to
77°F
(25°C)
(
max. 104°F / 40°C
).
Refer to Section 4.5.
Check for
sufficient floor load capacity
before installing the UPS and the Battery.
Refer to Section 4.1.1.
For Battery installation follow the local codes and the recommendation of the Battery supplier.
Note!
Operation at temperatures higher than 77°F (25°C) will reduce Battery life.
Potential consequences are explained in the User Manual to Section 9.1.4: read and understand
them.
The TLE Scalable Series 40 to 150 UPS can radiate radio frequency energy.
Although some RFI (Radio Frequency Interference) filtering is inherent to the UPS there is no guarantee that the
UPS will not influence sensitive devices such as cameras and monitors that are positioned close by.
If interference is expected, the UPS should be moved away from the sensitive equipment.
Positioning of the UPS TLE Scalable Series 40 to 150
Fig. 4.4.1-1 TLE Scalable Series 40 to 150 – Positioning of the UPS
Clearance around the front of the unit should be
sufficient to enable free passage of personnel
with the doors fully open and to allow sufficient
airflow to the door vents.
Check section 110-26(A) of the NEC code for
specific requirements.
To guarantee proper cooling and exhausted air
exchange,
it is mandatory
to maintain the
following minimum distances:
Rear side:
2”
(50mm)
Top of the UPS:
20”
(500mm)
A single-phase power outlet (120Vac) should be
provided near the UPS for connection of power
tools, test equipment or connectivity devices.
This outlet must be grounded.
Min.
20" / 500mm
Min.
2"
50mm