19/54
TLE Scalable Series 40 to 150 UL S1
UPS Installation Guide / REV-B
4.5
Ventilation and cooling
Fig. 4.5-1 Installation on plain floor
Fig. 4.5-2 Installation on raised floor
The heat produced by the UPS is transferred to the environment by its ventilation.
Air inlets for UPS ventilation are located on the front of the UPS, while air outlets are on top and rear of the cabinet.
A suitable ventilation or cooling system must be installed to extract the heat from the UPS room.
Note!
Do not put anything on the top of the cabinet.
20” (500mm) of air clearance from the top must be left free of any object for a sufficient exhausted
air exchange, proper cooling, service access and safety.
Air filtering systems could be required when the UPS operates in a dirty environment.
In order to prevent overheating of the UPS, the available air intake flow rate must exceed the total air exhaust
flow rate requirement of the UPS system.
Contact your
ABB Service Center
for appropriate solutions.
The below table indicates the heat dissipation at full Load at
PF = 0.9 & 1
and charged Battery, up to
3280 ft
(1000
m) altitude, for cooling air
77°F
(25°C) to
86°F
(30°C).
UPS model
Losses
Cooling air flow
VFI
SEM (Super Eco Mode)
VFI
PF = 0.9
PF = 1
PF = 0.9
PF = 1
PF = 0.9
PF = 1
TLE Scalable Series 150/40
6005 BTU/hr
1.760 kW
6142 BTU/hr
1.800 kW
1841 BTU/hr
0.540 kW
1911 BTU/hr
0.560 kW
872 CFM
513 m
3
/h
892 CFM
525 m
3
/h
TLE Scalable Series 150/50
7507 BTU/hr
2.200 kW
7677 BTU/hr
2.250 kW
1962 BTU/hr
0.575 kW
2047 BTU/hr
0.600 kW
1090 CFM
642 m
3
/h
1115 CFM
656 m
3
/h
TLE Scalable Series 150/80
11738 BTU/hr
3.440 kW
12011 BTU/hr
3.520 kW
3139 BTU/hr
0.920 kW
3276 BTU/hr
0.960 kW
1705 CFM
1003 m
3
/h
1744 CFM
1027 m
3
/h
TLE Scalable Series 150/100
15013 BTU/hr
4.400 kW
15355 BTU/hr
4.500 kW
3583 BTU/hr
1.050 kW
3753 BTU/hr
1.000 kW
2180 CFM
1283 m
3
/h
2230 CFM
1313 m
3
/h
TLE Scalable Series 150/120
18016 BTU/hr
5.280 kW
18426 BTU/hr
5.400 kW
4299 BTU/hr
1.260 kW
4504 BTU/hr
1.320 kW
2616 CFM
1540 m
3
/h
2676 CFM
1575 m
3
/h
TLE Scalable Series 150/150
22520 BTU/hr
6.600 kW
23544 BTU/hr
6.900 kW
5374 BTU/hr
1.575 kW
5630 BTU/hr
1.650 kW
3271 CFM
1925 m
3
/h
3419 CFM
2013 m
3
/h
Note!
The ventilation and cooling system shall be rated as for operation in VFI mode.