APPENDIX C - MINILINK POLLING DEVICE CONFIGURATION
18
Operator Interfaces SD
Con
fi
guration Screen #5 - Maverick Testing
Polling Unit Config
Maverick Testing
Disabled: YES
Use < Or > To Change
S
elect YES or NO. Disabling the Maverick Testing allows known
troubled zone(s) to continue voting without causing a Maverick
alarm. In other words, all zones are included in the voting regardless
of whether they are more than four degrees from setpoint.
MiniLink PD Con
fi
guration Screens
Con
fi
guration Screens #6-65 - Alarm Polling
Polling Unit Config
Enable Alarm Polling
Unit XX: YES
Use < Or > To Change
S
elect YES or NO. Enabling Alarm Polling allows any alarm from
the loop to be polled. You must set this for each controller on the loop.