SETPOINTS
Pioneer Gold 1.10 & 2.05 Touch Screen Operator Interface
2-15
Heating Setpoints
•
Occupied Heating
— Sets the Heating Setpoint.
Default: 70
°
F; Range: 55-85
°F
•
Unoccupied Heating
—Sets the Unoccupied Heating
Setpoint. Default: 65
°
F; Range: 55-85
°F
•
Heating Enable Deadband
—How far away from
Setpoint to generate or remove Call.
Default: 1
°F;
Range: 1-5
°F
•
Supply Air Heating Setpoint
—Default: 90
°F;
Range: 55-120
°F
•
Auxiliary Heat Deadband
— Space Temp has
to be this far below setpoint before Aux Heat can
energize. Default: 5
°
F; Range: 1-10
°F
•
Space Supply Heat Reset Setpoints
•
Space Hi Reset
—If Space is at or above this
value, SAT is at High Reset Value. Default:
72
°
F; Range: 55-85
°F
•
Space Lo Reset
—If Space is at or below this
value, SAT is at Low Reset Value. Default:
69
°
F; Range: 55-85
°F
•
Supply Hi Reset
— High Supply Air Setpoint.
Default: 100
°
F; Range: 55-120
°F
•
Supply Lo Reset
—Low Supply Air Setpoint.
Default: 90
°
F; Range: 55-120
°F
Dehumidification Setpoints
•
Dehumidification Enable
—If Space RH is above
this value, Unit will go into Dehumidification Mode.
Default: 50
%
; Range: 40-60
%
•
Dehumidification Lockout
—
If the Space Temp
is below this value, the Dehumidification will be
locked out. Default: 55
°
F; Range: 35-75
°F
•
Supply Air Reheat Setpoint
—
In the Modulating
Reheat mode, the controller will try to maintain this
setpoint. Default: 70
°
F; Range: 55-120
°F
Economizer Setpoints
•
Economizer Cooling Enable
—If Entering Water
Temperature is Below this value, the Economizer
can be used for “Free” Cooling. Default: 45
°F;
Range: 45-60
°F
•
Economizer Heating Enable
—
If the Entering
Water Temperature is Above this value, the
Economizer can be used for “Free” Heating.
Default: 85
°
F; Range: 75-90
°F
•
Water Econ Cooling Failure Time &
Water Econ Heating Failure Time
If the waterside economizer is enabled for cooling
or heating, the failure time is the time period before
it switches to Compressor Cool or Heat. Setting the
value to 255 will disable the timer so the waterside
economizer will run indefinitely in that mode and
never timeout. Default: 10
minutes
; Range: 10-255
minutes
Accessing & Entering Setpoints
Compressor Setpoints
•
Minimum On Time
—Compressor must run this much
time before it can turn off. Default: 180 seconds;
Range: 120-255 seconds
•
Minimum Off Time
—
Compressor must remain off this
much time before it can turn on.
Default: 120 seconds;
Range: 60-255 seconds
•
Interstage On Delay
—
If Stage 1 is energized, the
controller must wait this much time before turning on Stage
2. Default: 60 seconds; Range: 30-255 seconds
•
Interstage Off Delay
—
If Stage 2 is energized, the
controller must wait this much time before turning off Stage
2. Default: 60 seconds; Range: 30-255 seconds
Supply Fan Setpoints
•
Supply Fan Minimum Speed
—This is the Low Fan
Speed setting for a 2 Speed ECM Fan. Default: 40%;
Range: 40-100%
•
Supply Fan Maximum Speed
—
This is the High Fan
Speed setting for a 2 Speed ECM Fan.
Default: 100%;
Range: 40-100%
CO
2
Setpoints
•
CO
2
Override—
If CO
2
is above this value, the OA
damper will be opened.
Default: 900ppm; Range: 500-
1500ppm
Glycol Percentage
This is the percentage of Glycol mixed in the Loop
water. It is needed to calculate Lockout setpoints.
Default: 0%; Range: 0-40%
Water Valve Opening Delay
This is the amount of time that the Water Valve needs
to be open before Compressor operation is allowed.
Default: 30 seconds; Range: 5-75 seconds
Space Sensor Maximum Setpoint Offset
This setpoint limits how much the user can adjust the
Cooling and Heating setpoints above and below the Room
Sensor temperature. Default: 0°F; Range: +/10°F
Sensor Calibrations
•
Space Temperature, Supply Temperature &
Space Humidity Sensor Calibrations—
You can
adjust the offset temperature when the sensor is reading
incorrectly. Enter a positive value to raise the reading
or a negative value to lower the reading. Default: 0°F;
Range: +/-20°F
User Occupancy Override Time
This setpoint allows the user to adjust the occupancy
override time for the Remote Touch Screen Temperature
and Humidity Sensor. Default: 120 minutes; Range: 0-120
minutes. Entering a 0 will disable the override.
2-27-19 - added defs for sensor
calibrations - space temp and supply
temp - 3/19/20 - added space RH sen
-