BACNET
®
MS/TP & IP PARAMETERS
Pioneer Gold 1.10 & 2.05 Controller Technical Guide
1-48
BACnet
®
MS/TP & IP Analog Values & Binary Inputs
Table 13: BACnet
®
MS/TP & IP Parameter Binary Inputs
BACnet
®
MS/TP & IP Analog Values
BACnet
®
Point #
Default
Limit
Range
BACnet
®
Point Name
BACnet
®
Description
Unit
AV:23
35
35-100
Supply Fan Minimum
Percentage
Minimum allowed output for a variable speed supply fan
Percent
AV:24
0
-20 - 20
Space Temp Offset
Temperature offset for the space sensor
Fahrenheit
AV:25
0
-20 - 20
Supply Temp Offset
Temperature offset for the supply temperature sensor
Fahrenheit
AV:26
0
-20 - 20
Space RH Offset
Relative humidity offset for the space sensor
Fahrenheit
AV:27
0
0 - 10
Space Sensor
Maximum Setpoint
Offset
Maximum allowed user setpoint adjustment on the
touchscreen temp/humidity sensor
Fahrenheit
AV:28
30
5 - 75
Water Valve Opening
Delay Time
Amount of time given for the water valve to open before
compressor operation is allowed
Seconds
AV:29
120
30 -
120
User Occupancy
Override Time
Amount of time unit stays in user occupancy override
Minutes
AV: 30
10
10-255
Waterside Econo
Cooling Failure Time
Amount of time unit stays in economizer mode before going
into compressor cooling.
Minutes
AV: 31
10
10-255
Waterside Econo
Heating Failure Time
Amount of time unit stays in economizer mode before going
into compressor heating.
Minutes
AV: 32
70
55-120
Supply Reheat
Setpoint
Temperature setpoint of the discharge air while in
dehumidification mode.
Fahrenheit
Table 12: BACnet
®
MS/TP & IP Parameter Analog Values, continued
BACnet
®
MS/TP & IP Binary Inputs
BACnet
®
Point #
BACnet
®
Point Name
BACnet
®
Description
BI: 1
G Thermostat Call
Status of the G input terminal
BI: 2
Y1 Thermostat Call
Status of the Y1 input terminal
BI: 3
Y2 Thermostat Call
Status of the Y2 input terminal
BI: 4
O Thermostat Call
Status of the O input terminal
BI: 5
W1 Thermostat Call
Status of the W1 input terminal
BI: 6
Dehumidistat Call
Status of the DH input terminal
BI: 7
Night Setback Enable
Status of the night setback enable input terminal
BI: 8
Night Setback Override
Status of the night setback override input terminal
BI: 9
Night Setback Tstat
Status of the night setback thermostat input terminal
BI: 10
Emergency Shutdown Status
Status of the emergency shutdown input terminal
BI: 11
Waterside Economizer
Status of the waterside economizer relay output
BI: 12
Compressor 1 Output
Status of the compressor 1 relay output
BI: 13
Compressor 1 2nd Step
Status of the compressor 1 second step relay output for a 2 stage compressor
BI: 14
Compressor 2 Output
Status of the compressor 2 relay output for a unit with 2 compressors
BI: 15
Supply Fan Low Speed
Status of the low speed supply fan relay output
BI: 16
Supply Fan High Speed
Status of the high speed supply fan relay output