Pioneer Gold 1.10 & 2.05 Controller Technical Guide
BACNET
®
MS/TP & IP PARAMETERS
1-47
BACnet
®
MS/TP & IP Analog Values
Table 12: BACnet
®
MS/TP & IP Parameter Analog Values
BACnet
®
MS/TP & IP Analog Values
BACnet
®
Point #
Default
Limit
Range
BACnet
®
Point Name
BACnet
®
Description
Unit
AV:1
900
500-
1500
CO
2
Setpoint
CO
2
setpoint to control the damper override output
PPM
AV:2
74
55-85
Occupied Cooling
Setpoint
Cooling mode enable setpoint when space is occupied
Fahrenheit
AV:3
79
55-85
Unoccupied Cooling
Setpoint
Cooling mode enable setpoint when space is unoccupied
Fahrenheit
AV:4
55
45-65
Supply Cooling
Setpoint
Temperature setpoint of the discharge air while in cooling
mode
Fahrenheit
AV:5
180
120-
255
Compressor Min On
Time
Minimum on time setpoint for compressor(s)
Seconds
AV:6
120
60-255
Compressor Min Off
Time
Minimum off time setpoint for compressor(s)
Seconds
AV:7
60
30-255
Compressor
Interstage On Delay
Interstage on delay setpoint when unit has more than one
compressor stage
Seconds
AV:8
60
30-255
Compressor
Interstage Off Delay
Interstage off delay setpoint when unit has more than one
compressor stage
Seconds
AV:9
75
55-85
Space Cooling Hi
Reset
High space temperature setpoint when using space/supply
reset control in cooling mode
Fahrenheit
AV:10
72
55-85
Space Cooling Lo
Reset
Low space temperature setpoint when using space/supply reset
control in cooling mode
Fahrenheit
AV:11
57
45-65
Supply Cooling Hi
Reset
High supply temperature setpoint when using space/supply
reset control in cooling mode
Fahrenheit
AV:12
53
45-65
Supply Cooling Lo
Reset
Low supply temperature setpoint when using space/supply
reset control in cooling mode
Fahrenheit
AV:13
70
55-85
Occupied Heating
Setpoint
Heating mode enable setpoint when space is occupied
Fahrenheit
AV:14
65
55-85
Unoccupied Heating
Setpoint
Heating mode enable setpoint when space is unoccupied
Fahrenheit
AV:15
90
55-120
Supply Heating
Setpoint
Temperature setpoint of the discharge air while in heating
mode
Fahrenheit
AV:16
72
55-85
Space Heating Hi
Reset
High space temperature setpoint when using space/supply
reset control in heating mode
Fahrenheit
AV:17
69
55-85
Space Heating Lo
Reset
Low space temperature setpoint when using space/supply reset
control in heating mode
Fahrenheit
AV:18
100
55-120
Supply Heating Hi
Reset
High supply temperature setpoint when using space/supply
reset control in heating mode
Fahrenheit
AV:19
90
55-120
Supply Heating Lo
Reset
Low supply temperature setpoint when using space/supply
reset control in heating mode
Fahrenheit
AV:20
50
40-60
Dehum Enable
Setpoint
Relative humidity setpoint for enabling dehumidification
setpoint
Relative
Humidity
AV:21
5
1-10
Aux Heat Deadband
Degrees Fahrenheit that the supply air must be under setpoint
for auxiliary heat to enable
Fahrenheit
AV:22
100
35-100
Supply Fan
Maximum Percentage
Maximum allowed output for a variable speed supply fan
Percent