Zone
Zone
WIRING
Pioneer Gold 1.10 & 2.05 Controller Technical Guide
1-14
Pioneer Gold Controller & Electric Heat Board Input/Output Maps
Input/Output Map
See
Table 4
for Pioneer Gold Controller Inputs/Outputs. Future
items are grayed out.
PIONEER GOLD CONTROLLER
DIGITAL INPUTS
G
Fan Call (TSTAT)
Y1
Compressor Stage 1 Call (TSTAT)
Y2
Compressor Stage 2 Call (TSTAT)
O
Cooling Call (TSTAT)
DH
Dehumidification Call (TSTAT)
W1
Heat Stage 1 (TSTAT)
NSB
Night Setback (TSTAT)
NSB OVR
Night Setback Override Input (TSTAT)
ESD*
Emergency Shutdown* (TSTAT)
NSB TH
Night Setback TSTAT Input (TSTAT)
COF
Condensate Overflow
COF2
Secondary Condensate Overflow
AUX
Auxiliary Fault Switch
HPS
High Pressure Switch
LPS
Low Pressure Switch
DI1
Air Flow Switch
WFS
Water Flow Switch (Future)
* NOT A FIRE/LIFE SAFETY DEVICE
ANALOG INPUTS
SPT
Suction Pressure
DPT
Discharge Pressure
EWT
Entering Water Temperature
LLT
Liquid Line Temperature
ECT
Evaporator Coil Temperature
HWT
Entering Hot Water Temperature (Future)
SAT
Supply Air Temperature
SPAT
Space Temperature
CO2
Space CO
2
TOUCH SCREEN INPUTS
SPAT
Space Temperature
SPAH
Space Humidity
UNIVERSAL INPUTS
UI1
LWT - Leaving Water Temperature
UI2
Spare
UI3
Spare
UI4
Spare
Table 4: Pioneer Gold Inputs & Outputs
DIGITAL OUTPUTS (24 VAC)
R/C
Thermostat Power (TSTAT)
ALM
Alarm Output
ALM1/ALM2 Alarm Dry Contact Output
Fan/Fan
Supply Fan Enable
Fan2/Fan
Supply Fan Stage 2 Enable
Y1/Y1
Compressor Stage 1
Y2/Y2
Compressor Stage 2
Y3/Y3
Compressor Stage 3 (Future)
RV/RV
Reversing Valve
W1/W
Electric Heat Stage 1
MV/MV
Motorized Water Valve/Pumps
HG/HG
HGRH Valve
WSE/WSE
WSE Valve
DI1
Spare
ANALOG OUTPUTS (0-10 VDC)
SFS
Supply Fan Speed
PUMP
Variable Speed Pump (Future)
MWV
Modulating Water Valve On/Off (Future)
DMPR OVR CO
2
Damper Override
AO1
Spare
AO2
Spare
COMMUNICATION TERMINALS
R/C
Extra Power Terminals
BACNET
WattComm, ModBus RTU, or BAS MS/TP
Terminal (Selectable)
TSTAT
Pioneer Gold Touch Screen Space / RH
Temperature Sensor
3 MODBUS
Ports
MODBUS Expansion Communication
Ethernet Port IP Communication (ASM02323 only)
ELECTRIC HEAT BOARD INPUTS
LIMIT
Limit (Hi) Switch
ELECTRIC HEAT BOARD OUTPUTS
HEAT 1
Electric Heat Stage 1 Relay
HEAT 2
Electric Heat Stage 2 Relay
Table 4, cont.: Pioneer Gold Inputs & Outputs