Code and
description
Cause
Measure
Not enough pressure differential across
the air proving switch, due to:
-
venting system
-
malfunction condensation
discharge
-
dirty burner
-
blocked heat exchanger
Check, after each fix, if the error reappears.
If the error reappears continue in finding
the cause.
-
Measure the pressure differential
across the air proving switch, refer to
Air pressure differential.
Venting system (see 8.7):
-
Make sure if the venting system is
compliant.
-
Make sure that the venting system has
no blockages.
-
Make sure if the air inlet screen has no
blockages.
Condensation discharge:
-
Make sure the condensate drain has
no blockages.
-
Make sure that the condensate drain is
connected to the waste water
discharge by an open connection.
Burner:
-
Make sure that the the burner is clean
(see 11.4.1).
-
Measure the pressure differential
across the air proving switch again. If
the pressure differential is insufficient,
clean the heat exchanger.
-
Use a multimeter to make sure that
the air proving switch is closed.
XAC-XXXX
(blocking error)
Fan error
Switch is closed when fan
is not running.
Damaged wiring/closed circuit.
-
Make sure that the wiring, between
the air proving switch and the
controller, is connected and not
damaged.
-
If necessary replace the wires or
reconnect the wires. Reset the
controller, when wires are replaced or
reconnected.
Air proving switch defect.
-
Make sure that the air proving switch
works properly.
-
If necessary, replace the air proving
switch.
-
When the air proving switch is
replaced and reconnected, reset the
controller.
0313279_TWISTER II_UKUK_
V1.1, 18-02-2019
77
Summary of Contents for TWI 35-200
Page 6: ...6...
Page 13: ...User part 0313279_TWISTER II_UKUK_V1 1 18 02 2019 13...
Page 14: ...14...
Page 16: ...16 User part...
Page 18: ...18 User part...
Page 25: ...Installation Maintenance and Service part 0313279_TWISTER II_UKUK_V1 1 18 02 2019 25...
Page 26: ...26 User part...
Page 34: ...34 Installation Maintenance and Service part...
Page 54: ...54 Installation Maintenance and Service part...
Page 56: ...56 Installation Maintenance and Service part...
Page 66: ...66 Installation Maintenance and Service part...
Page 72: ...72 Installation Maintenance and Service part...
Page 80: ...80 Installation Maintenance and Service part...
Page 87: ...13 6 Declaration of conformity 0313279_TWISTER II_UKUK_V1 1 18 02 2019 87...