334 | Alarm Types and Sources
Aprisa SRi User Manual 1.1.0
Event
ID
Event Display
Text
Default
Severity
Configuration
Type
Function
Recommended Actions
46
Port 3 Eth Data
Transmit Errors
warning(4)
Error Ratio Type
Alarm to indicate that
Ethernet port 3 transmitted
output signal contains errors
at a higher rate than the
defined error rate threshold.
Check Ethernet cable and
connector. Check switch
port or RTU is active. Check
IP and VLAN configuration.
47
Port 3 Eth Port
Down
critical(1)
Sample Duration
Type
Alarm to indicate that
Ethernet port 3 has no
detected connection during
the defined duration period.
Check the cable and
connector. Check switch
port or RTU is active. Check
Ethernet Port speed/duplex
configuration.
48
Port 4 Eth No
Receive Data
warning(4)
Sample Duration
Type
Alarm to indicate that
Ethernet port 4 has no
received input signal in the
defined duration period.
Check Ethernet cable and
connector. Check switch
port or RTU is active. Check
IP and VLAN configuration.
49
Port 4 Eth Data
Receive Errors
warning(4)
Error Ratio Type
Alarm to indicate that
Ethernet port 4 received
input signal contains errors
at a higher rate than the
defined error rate threshold.
Check Ethernet cable and
connector. Check switch
port or RTU is active. Check
IP and VLAN configuration.
50
Port 4 Eth Data
Transmit Errors
warning(4)
Error Ratio Type
Alarm to indicate that
Ethernet port 4 transmitted
output signal contains errors
at a higher rate than the
defined error rate threshold.
Check Ethernet cable and
connector. Check switch
port or RTU is active. Check
IP and VLAN configuration.
51
Port 4 Eth Port
Down
critical(1)
Sample Duration
Type
Alarm to indicate that
Ethernet port 4 has no
detected connection during
the defined duration period.
Check the cable and
connector. Check switch
port or RTU is active. Check
Ethernet Port speed/duplex
configuration.
13
Port 1 Serial Data
No Receive Data
warning(4)
Sample Duration
Type
Alarm to indicate that the
RS-232 port 1 has no received
input signal in the defined
duration period.
Check serial ports settings,
check serial cable and
connector.
14
Port 1 Serial Data
Receive Errors
warning(4)
Error Ratio Type
Alarm to indicate that the
RS-232 port 1 received input
signal contains errors at a
higher rate than the defined
error rate threshold.
Check serial ports settings,
check serial cable and
connector.
52
Port 2 Serial Data
No Receive Data
warning(4)
Sample Duration
Type
Alarm to indicate that the
RS-232 port 2 has no received
input signal in the defined
duration period.
Check serial ports settings,
check serial cable and
connector.
53
Port 2 Serial Data
Receive Errors
warning(4)
Error Ratio Type
Alarm to indicate that the
RS-232 port 2 received input
signal contains errors at a
higher rate than the defined
error rate threshold.
Check serial ports settings,
check serial cable and
connector.
63
USB Port Serial
Data No Receive
Data
warning(4)
Sample Duration
Type
Alarm to indicate that the
USB port has no received
input signal in the defined
duration period.
Check serial ports settings,
check USB serial cable and
adapter, check serial
connector.
64
USB Port Serial
Data Receive
Errors
warning(4)
Error Ratio Type
Alarm to indicate that the
USB port received input
signal contains errors at a
higher rate than the defined
error rate threshold.
Check serial ports settings,
check USB serial cable and
adapter, check serial
connector.