4EVAC Compact 500 quick guide
DoP OD 16.47
Author:
DD
Design revision:
2.0
Page 12 of 33
6.5.1.
EVAC out
Activated (closed) on EVAC mode, where at least one zone of the voice evacuation system is transmitting
an automatic EVAC message or LIVE EVAC signal from the fireman microphone.
6.5.2.
FAULT out
Activated (closed) while the fault status is reported by the voice evacuation system.
Also activated when the Compact 500 is not powered.
6.5.3.
RESET out
Activated (closed) immediately after a manual reboot of the Compact 500 main unit. The active pulse length
is configurable from 0 (disabled) to 5000ms in the configuration settings.
GPI / GPO
8 x general purpose input (pull-down), 8 x general purpose output (open collector)
GPIs and GPOs are programmable in the configuration file. The GPI and GPO can be linked to any system
events to trigger or follow system events.