3.
Put the battery in the battery compartment.
4.
Make sure that all battery leads are long enough and have rubber insulating caps on their ends.
Caution! Be careful! The negative pole of the battery connector is directly connected to ground potential
and the entire metal housing of Compact 500. Dropping an unprotected battery lead on any part of the
hardware, housing or battery brings high risk of a short-circuit and may damage the hardware and the
battery. The high electrical current from the battery under short-circuit condition may cause rapid battery
discharge and instant heat production. This may also destroy hardware components, cause serious battery
capacity degradation or battery damage, cause fire and may be a potential risk to your health.
5.
Connect the battery jumper (short black) between the negative (-) pin of battery A and the positive
(+) pin of battery B.