Page 17 of 33
Analog audio input (BGM)
Two analog audio inputs, balanced, line-level.
Connect your auxiliary audio source for background music or low a priority external paging microphone
here.
NOTE: By default, the Compact 500 includes an integrated fireman microphone, which occupies analog
audio input 2. If your system does not require an integrated fireman microphone feature, you can disable
it in the configuration settings and use analog audio input 2 as an external audio input for background
music.
Network ports
4EVAC Compact 500 offers 5 ports (RJ-45) for network connections between distributed parts of the 4EVAC
Voice Evacuation System:
2 x G-Net ports (global network)
3 x L-Net ports (local network)
The 4EVAC network features a full duplex RS-422 data link and 24V DC power to remote devices.
If you’re building a distributed system using the 4EVAC network, you should make physical links between
devices using the right cables. Cabling should meet the following requirements:
1.
Crossover twisted-pair cable (compatible with Ethernet crossover)