Pag. 5
DUALNET—6 INSTRUCTION MANUAL
ENGLISH
PCB Component Description
Number
Description of functions (See fig. 1)
1
S1: Connector for tamper button
(see note “a” below)
2
LED CPU: LED which indicates the microprocessor status
3
SIM Card Socket: To insert Local SIM card.
4
LED 2: Front panel power LED status
5
GSM module
6
DN-8Z Socket
: Input Connection for 8 zone hardwire expansion module
DN-8Z
7
BATTERY TEMP: CR1220 battery case
8
PSTN Telephone OUT : Telephone line output for home phone
12
Tamper button
9
PSTN Telephone IN: Telephone line input
(see note “b” below)
10
230Vac. Mains input terminal one Amp delay action fuse.
11
FUSE: (A) 250V 2Amp. Delayed action. (B) 250V 3.15 Amp. immediate
(a) Note: Before powering up the control panel, be sure that the tamper bridge connector is inserted on
the tamper switch connector (1) with the jumper provided. After you have terminated the programming,
connect the tamper switch (12) to the plug (1), fix the control panel cover in place and exit the program-
ming mode.
(b) Connect the PSTN telephone line to the control panel. Be sure that this line is direct and not through
a PBX system. If connected after the ASDL station use an appropriate line filter.
Attention: For the connection of terminals 22 to 28 with the touch screen keypad DN-6KP, it is necessary
to use an adequately shielded and ground cable. Type normally used in alarm installations 2 x 0.50 mm.
Double balanced line connection
with 2 wires.
With control panel in stand-by mode, only R2 will be detected.
When control panel is triggered, both the R1 and R2 will be detected.
In the case of a tamper trigger, infinite resistance will be detected.
All DUALNET-6 hardwire zones have double balance lines and can detect the difference between an
alarm trigger and a tamper trigger. For correct function, they must be wired as shown below.
This is a double balance line connection
Without the tamper protection.
Panel Terminals
Contact NC
Alarm trigger output
(NC)
Balanced lines
R2 = 2,2 K ohm
R1 = 2,2 K ohm
If tamper control is not necessary,
use the schematic diagram on the
right.
Panel Terminal
Sensor Terminal
Alarm output
(NC)
Balanced Line
R2 = 2,2 K ohm
R1 = 2,2 K ohm
Tamper output
(NC)
Hardwire, double balance line, zone connections: