3-4
z
If there is a grounding strip in the Ethernet switch installation environment, attach one end of the
yellow-green protection grounding cable to the grounding screw of the grounding strip and fasten
the captive nuts. The grounding cable of a switch shall be connected to the project ground of the
equipment room.
Figure 3-3
Connect the protection grounding cable to the grounding strip
Power input
Ethernet
Switch
Grounding strip
Protection grounding cable
Grounding screw
Ethernet
Switch
Ethernet
Switch
z
If there is no grounding strip but earth nearby and the grounding body is allowed to be buried, you
can simply hammer an angle iron or steel pipe no shorter than 0.5m into the earth. In this case, the
yellow-green protection grounding cable should be welded with the angle iron (steel pipe) and the
joint should be processed against eroding.
Figure 3-4
Connect the protection grounding cable to the grounding body nearby
Power input
Ethernet Switch
Grounding screw
Angle steel
Ground
Protection grounding cable
z
If there is no grounding strip and no grounding body can be buried, the AC-powered Ethernet
switch can be grounded through the PE wire of the AC power supply. In this case, make sure that
the PE wire of the AC power supply has been well grounded at the power distribution room or AC
power supply transformer side.