Installation Guide for the 2GIG EDGE Security Panel
48
Timers, Delays & Counts
Q201: Exit delay, in seconds
Configures the number of seconds for the Exit Delay countdown. Different times may be programmed for each Smart Areas. (Smart Areas feature
must be enabled (Q107) for values for S2-S4 to affect the system) This is the amount of time occupants have to exit the building through a door after
arming the system. The doors programmed as Exit/Entry 1 and Exit/Entry 2 use this timer. When the user arms the system, the countdown starts.
The 2GIG EDGE Panel beeps once every two (2) seconds during the countdown. For the last 10 seconds, the beeps speed up to warn occupants
that they have less than 10 seconds to exit the premises.
Choose one of these options:
»
45-120 Seconds:
Choose a value between 45 and 120 seconds.
»
† ‡
60 Seconds:
For compliance with ANSI/SIA CP-01-2010, the default Exit Delay feature is set to 60 seconds.
NOTE:
Arming the system from a remote location with a web-enabled device, such as a computer or smart phone, does NOT initiate the
Exit Delay countdown.
Q202: Entry delay 1, in seconds
Configures the number of seconds for the Entry Delay 1 timer. Different times may be programmed for each Smart Areas. (Smart Areas feature
must be enabled (Q107) for values for S2-S4 to affect the system) This specifies the amount of time occupants have to disarm the system after
entering the premises through a door. Typically, the primary entrance programmed as an Exit/Entry 1 door uses this time. When the user enters
the premises, the countdown timer starts. The 2GIG EDGE Panel beeps once every two (2) seconds during the countdown.
Choose one of these options:
»
30-240 Seconds:
Choose a value between 30 and 240 seconds.
»
† ‡
30 Seconds:
For compliance with ANSI/SIA CP-01-2010, the default Entry Delay 1 feature is set to 30 seconds.
Q203: Entry delay 2, in seconds
Configures the number of seconds for the Entry Delay 2 timer. Different times may be programmed for each Smart Areas. (Smart Areas feature must
be enabled (Q107) for values for S2-S4 to affect the system) This specifies the amount of time occupants have to disarm the system after entering the
premises through a door. Typically, secondary entrances that require a slightly longer entry time are programmed as an Exit/Entry 2 door. For example,
a back, side, or garage entry door. When a user enters the premises while the system is armed, the Entry Delay 2 countdown starts. The 2GIG EDGE
Panel beeps once every two (2) seconds during the countdown.
Choose one of these options:
»
30-240 Seconds:
Choose a value between 30 and 240 seconds.
»
†‡
45 Seconds:
For compliance with ANSI/SIA CP-01-2010, the default Entry Delay 2 feature is set to 45 seconds.
Q204: Alarm cancel time, in minutes
Configures the system to transmit a cancellation report to the Central Station whenever an alarm is canceled by a user within the amount of time
specified here. To learn how to change the setting for the alarm information that displays on the touchscreen, see “Q122: Alarm cancel display” below.
»
† ‡
5 Minutes:
For compliance with ANSI/SIA CP-01-2010, the minimum required setting is 5 minutes. This can be extended to a
greater number of minutes without affecting compliance.
»
6-254 Minutes:
Enter a value between 6 and 254 minutes.
»
255:
To transmit a cancellation report anytime the system is disarmed after an alarm, enter 255.
Q205: Alarm abort window transmission delay
Configures the amount of time the system will wait to initiate the digital transmission when an alarm condition is triggered. This setting specifies
the number of seconds the user has to manually abort the alarm, in the event of a false alarm.
NOTE:
The transmission delay can be increased to 45 seconds without affecting ANSI/SIA CP-01 compliance only if the combination of
Q205 and
Q202: Entry delay 1, in seconds (30-240)
in
Q203: Entry delay 2, in seconds (30- 240)
does not exceed one (1) minute.
Choose one of these options:
»
15 seconds:
The system waits 15 seconds to initiate the dialer.
»
† ‡
30 seconds:
For compliance with ANSI/SIA CP-01-2010, the default minimum setting is 30 seconds. This setting can be increased
to 45 seconds without affecting compliance only if the combination of this setting.
»
45 seconds:
The system waits 45 seconds to initiate the dialer.
Q206: Burglary bell cutoff time
Defines the amount of time the system sounds the burglary alarm after the alarm is activated. After the time set here expires, the alarm siren
shuts OFF.
NOTE:
This setting only affects the 2GIG EDGE Panel alarm. It does not affect any auxiliary alarms that may be installed. Typically,
auxiliary alarms are set to sound for an unlimited amount of time.